COOL operation
Four-way valve/OFF
Initial
COOLING
NO
NO
NO
NO
NO
NO
YESw8
YES
YES
YES
YES
YES
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
Vane initial
setting
Vane
55 deg downward angle
70 deg downward angle
Fan speed
LOW
Downward discharge
1 hour
Vane setting notch
Vane horizontal
airflow
Compressor
thermostat
ON
Allowance
cancel
3-minute
time delay
6-minute
time delay
3-minute
compressor operation
Coil frost
prevention
Cooling area
10-minute
compressor operation
Allowance cancel
Coil frost
protection
16-minute
compressor operation
Indoor pipe
temperature is
1°C or lower
Compressor ON
1
Coil frost
prevention
Compressor OFF
Indoor coil
tempreature is
10°C or higher
3-minute
time delay
Coil frost
prevention release
Allowance
period
6 minute
time delay
Allowance set
1 min continue
Coil frost protection
FAN speed
LOW
FAN speed
LOW 5 min
elapse
Outdoor unit
trouble
w9
w10
w11
COOLING OPERATION
w8 When operation stops or changes to cooling or dry mode, the auto vane tums to a horizontal angle. If operation changes
during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10 After 3 minute compressor operation, if the indoor coil thermistor reads -15°C or below for 3 minutes, the compressor will
stop for 6 minutes.
w11 Cooling area : Indoor coil temperature is more than 5 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 5 degrees below the room temperature.
FAN area : Indoor coil temperature is within 5 degrees either way of the room temperature.