6-4. STANDARD OPERATION DATA
PUZ-HA30NHA
Representative matching
PKA-A36FA
Mode
COOLING HEATING
Total Capacity BTU/h
34,200 38,000
Input W
2,950 3,100
Electrical circuit
Indoor unit model
Phase
Single
Cycle
60Hz
Voltage
230V
Current
0.52A
Outdoor unit model
PUZ-HA36NHA
Phase
Single
Cycle
60Hz
Voltage
230V
Current
Refrigerant circuit
Discharge pressure MPa
Suction pressure MPa
Discharge temperature °C
Condensing temperature °C
Suction temperature °C
Ref. Pipe length m
Discharge pressure PSIG
Suction pressure PSIG
Discharge temperature °F
Condensing temperature °F
Suction temperature °F
Ref. Pipe length ft
side
Indoor
Intake air temperature DB °C
Intake air temperature WB °C
Discharge air temperature DB °C
side
Outdoor
Intake air temperature DB °C
Intake air temperature WB °C
side
Indoor
Intake air temperature DB °F
Intake air temperature WB °F
Discharge air temperature DB °F
side
Outdoor
Intake air temperature DB °F
Intake air temperature WB °F
SHF
BF
PKA-A30FA
COOLING HEATING
12.7 A
2.60
0.91
69.0
44.5
3.2
7.6
377
132
156
112
38
25
26.7
19.4
13.7
35
23.9
80
67
57
95
75
0.77
0.11
13.4 A
2.81
0.73
76.1
47.0
2.7
7.6
407
106
169
117
37
25
21.1
15.6
42.7
8.3
6.1
70
60
109
47
43
30,000 32,000
2,730 3,460
PKA-A36FA
PKA-A30FA
12.1 A
2.57
0.83
70.6
43.5
10.6
7.6
372
120
159
110
51
25
26.6
19.3
12.1
35
25.1
80
67
54
95
77
0.70
0.08
13.8 A
3.21
0.76
83.0
51.5
4.0
7.6
465
110
181
125
39
25
21.1
15.6
44.6
8.3
6.1
70
60
112
47
43