Indoor Installation Manual
11
6. Electrical work
Function table (table 1)
Select unit number 00
Mode Settings Mode no. Setting no.
Initial setting
setting
Power failure automatic recovery Not available
01
1
Available *1 2 Ο*2
Indoor temperature detecting Indoor unit operating average
02
1 Ο
Set by indoor unit’s remote controller 2
Remote controller’s internal sensor 3
LOSSNAY connectivity Not Supported
03
1 Ο
Supported (indoor unit is not equipped with outdoor-air
intake)
2
Supported (indoor unit is equipped with outdoor-air intake) 3
Power voltage 230V
04
1 Ο
208V 2
Selectunitnumbers01to03orallunits(AL[wiredremotecontroller]/07[wirelessremotecontroller])
Mode Settings Mode no. Setting no.
Initial setting
setting
Filter sign 100Hr
07
1
2500Hr 2 Ο
Noltersignindicator 3
Fan speed Silent (low ceiling)
08
1
Standard 2 Ο
High ceiling 3
No. of air outlets 4 directions
09
1 Ο
3 directions 2
2 directions 3
Installedoptions(high-efciencylter) Not supported
10
1 Ο
Supported 2
Up/downvanesetting
Downward setting (vanes angle setup 3)
11
1
Middle setting (vanes angle setup 1)
2 Ο
Draft-less setting (vanes angle setup 2) *4
3
3D i-see Sensor positioning
Position 1
12 *3
1
Position 2
2
Position 3 (Default)
3 Ο
3D i-see Sensor ceiling height setting
(when installing the 3D i-see Sensor panel)
Low ceiling (ceiling height: less than 2.7 m, 8.9 ft)
26
1
Standard (ceiling height: 2.7-3.5 m, 8.9-11,5 ft) 2 Ο
High ceiling (ceiling height: 3.5-4.5 m, 11,5-14.8 ft) 3
Fan speed during the cooling thermostat is OFF Setting fan speed
27
1 Ο
Stop 2
Extra low 3
*1 When the power supply returns, the air conditioner will start 3 minutes or 1 minute later (hinge on Outdoor unit).
*2 Power failure automatic recovery initial setting depends on the connecting outdoor unit.
*3 When the 3D i-see Sensor corner panel position is changed, change this mode. Refer to page 17.
*4 Because condensation may form, do not use this setting in a high-temperature, high-humidity environment.