9 OPERATION FLOW-CHART
START
STOP
EMERGENCY
ALL STOP
COOL OPERATION
DRY OPERATION
POWER SUPPLY
Live
ON/OFF
button ON
Abnormal
operation mode
MODE SELECT
button
POWER lamp ON
Protection device
Self hold reset
Protection device
Self hold
Self-diagnostic function
Indicate & Memory
NO
NO
YES
<Note 4>
<Note 5>
NO
1
NO
YES
YES
COOL
DRY
1. Main operation
Note1. The unit starts operation by pressing the ON/OFF switch when unit is OFF.
During operation, the unit stops operation by pressing the ON/OFF switch.
In addition, operation can be turned ON/OFF with the centralized remote controller or the remote switch.
Note2. The factors which cause “abnormal operation mode” are as follows.
Outdoor unit abnormal operation.
Fault of room temperature thermistor(RT1).
Fault of indoor coil thermistor(RT2).
Indoor coil frost protection mode.
Fault of drain sensor(DS).
Drain water overflow prevention mode.
Refer to page 30 for abnormal operation, mode details.
Note3. The indoor fan runs on the low speed for 1 minute to eliminate remaining heat.
Note4. The compressor will not start for 3 minutes after the stop.
Note5. The thermostat is continuously ON during the test run.
Note6. Refer to page 31 for coil frost protection.
Note7. Range A : Indoor coil temperature is more than 5 degrees above room temperature.
Range B : Indoor coil temperature is within 5 degrees either way of room temperature.
Range C : Indoor coil temperature is more than 5 degrees below room temperature.