[ VII Microprocessor Control ]
- 11 -
HWE08010 GB
In the air : Detected that the float switch is OFF for 15 seconds.
2. Dry operation
1. Termoregulating function
(1) Thermo regulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermo regulating signal and the room temperature (TH21).
Dry thermo ON Room temperature desired temperature + 2°F
Dry thermo OFF Room temperature desired temperature
(2) Frozen prevention control
No control function
2. Fan
(1) Indoor fan operation controlled depends on the compressor conditions.
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display DRY.
3. Press the [Set Temperature] button to set the desired tempera-
ture.
The set temperature changes 2°F when the [Set Temperature]
button is pressed one time. Dry 67 to 87°F
Room temperature
3 min. passed since starting operation
Dry thermo
ON time (min)
Dry thermo
OFF time (min)
Thermo regulating signal Room temperature (T1)
Over 64°F
ON
T1 83°F 9 3
83°F > T1 79°F 7 3
79°F > T1 75°F 5 3
75°F > T1 3 3
OFF Unconditional 3 10
Less than 64°F Dry thermo OFF
Dry thermo Fan speed notch
ON [Low]
OFF
Excluding the following Stop
Room temp. < 64°F [Low]
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET