Service Manual

6
OCH636B
2-5. LOW AMBIENT COOLING
Precautions for low ambient cooling
If the outdoor temperature is 23°F or lower during cooling operation, install an optional air guide to prevent wind from
blowing into the outdoor unit.
Install the outdoor unit in a location where wind will not blow onto the back of the unit.
To prevent damage to the parts, be sure to install the unit, turn on the main power, and perform service in an environment
where the ambient temperature is 0°F or higher.
In order to protect the compressor and electrical components, do not turn o󰀨 the circuit breaker if the unit is installed in an
environment where the ambient temperature is 0°F or lower.
It needs at least 12 hr standby to operation in order to warm the electrical parts.
Note: During cooling operation under low ambient temperature, the bottom fan motor of A36, 42N stops occasionally. This is
an intended feature, not a malfunction.