Engineering Manual
PAC-SH91MK-E/PAR-SA92MW-E/PAR-SL93B-E
Function Selection
6
This setting is available only for Mr. Slim model. CITY MULTI model can be set by dip switch of indoor/outdoor
control circuit board. Refer to technical data of CITY MULTI model to set dip switch.
Each function can be set according to necessity using the remote controller.
The setting of function for each unit can only be done by the remote controller.
Select function available from the Table3. Function selection using wireless remote controller
is available only for refrigerant system with wireless function. Refrigerant address cannot
be specified by the wireless remote controller.
The article below describes how to set “LOSSNAY connectivity” into “supported
(indoor unit is not equipped with outdoor-air intake)” in Table 3 as an example.
1 Go to the function select mode
Press the button F twice continuously.
(Start this operation from the status of remote controller display turned off.)
CHECK is lighted and “00” blinks.
Press the temp button C once to set “50”. Direct the wireless remote
controller toward the receiver of the indoor unit and press the button A.
2 Setting the unit number
Press the temp button C and D to set the unit number “00”. Direct
the wireless remote controller toward the receiver of the indoor unit and
press the button B.
3 Selecting a mode
Enter 03 to change the LOSSNAY connectivity setting using the C and
D buttons. Direct the wireless remote controller toward the receiver
of the indoor unit and press the button A.
Current setting number: 1=1 beep (1 second)
2=2 beeps (1 second each)
3=3 beeps (1 second each)
W If a mode number that can not be recognized by the unit is entered,
3 beeps (3 beeps of 0.4 seconds duration)will be heard.
Reenter the mode number selecting.
W If the signal was not received by the sensor or an error occurred during
transmission, you will not hear a beep or a “double beep” may be heard.
Press the button again.
4 Selecting the setting number
Use the C and D buttons to change the LOSSNAY connectivity setting
to 02. Direct the wireless remote controller toward the sensor of the indoor
unit and press the button A.
→ At this time, current setting number for selected mode number will be output
by the interrupted buzzer sounds and the blinks of operation indicator.
Output : setting number = 1 → beep beep (0.4 second + 0.4 second) ×1
2 → beep beep (0.4 second + 0.4 second) ×2
3 → beep beep (0.4 second + 0.4 second) ×3
W If a setting number that can not be recognized by the unit is entered, 3 beeps
(3 beeps of 0.4 seconds duration) will be heard (unit will beep only).
Reenter the setting number selecting.
W If the signal was not received by the sensor or an error occurred during
transmission, you will not hear a beep or a “double beep” may be heard.
Press the button again.
W If the number that can not be set is input, the former setting number will be set.
5 To select multiple functions continuously
Repeat steps 3 and 4 to change multiple function settings continuously.
6 Complete function selection
Direct the wireless remote controller toward the sensor of the indoor unit
and press the button E.
CHECK
min
h
h
h
h
h
NOTE : Whenever changes are made to the function settings after construction or
maintenance, be sure to record the added functions with an “
○
”, in the
“Check” column provided on the chart.