Engineering Manual
Multi-functional Casement PAC-SJ41TM-E
Electrical work of main unit
Temporary installation
●Fix the 2 screw with washer (black) 2 to each position.
(drain pipe corner position and to its opposite corner).
●Align the direction of the Multi-functional casement 1 according to the
label for checking the installation position attached inside the
Multi-functional casement 1.
Note: If installed in improper direction, parts damage, wind leakage,
or dew drop may result.
●Hook the hole of the Multi-functional casement 1 to the
screw with washer (black) 2 and hand tight.
Note: Be sure to use two persons for this work.
Fixing
●Temporarily secure the 2 screws with washers 2, and
also the other 2 screws with washers 2, and then tighten
these screws with washers 2 after making sure that the position
of Multi-functional casement 1 is correct.
●Be sure to do the wiring (indoor/outdoor unit connection cable,
remote controller cable, etc.) before installing the Multi-functional
casement 1:
Note: Wiring after installing the Multi-functional casement 1 will be difficult.
Caution
Temporarily secure the 4 screws with washers.
●Tightening the screws without temporarily securing
them could damage the screws with washers, or
cause air leakage.
Caution
When tightening the screw with washer 2, tighten it
at a torque of 2.8 to 3.6 N•m (2.1 to 2.6 ft•lbs) or less.
Never use an impact screwdriver.
●It may result in parts damage.
Refrigerant pipe
Main unit
Drain pipe
Multi-functional
casement plates
(at 4 corners)
Note: The label for checking
installation position is
inside the Multi-functional
casement.
Screw with
washer 2
Screw with
washer 2
(Hand tightening)
Multi-functional
casement 1
3 Installation of Multi-functional casement
Multi-functional
casement 1
Ceiling
Main unit
The gap must be in a range from 17mm(11/16in.) to 22mm(7/8in.).
If out of range, it can cause malfunction.
Hole size on ceiling
(11/16 -7/8in.)
Gauge
(Insert to the Multi-functional casement)
17 mm
+5
0
Screw 3
Grille securing bracket 4
Screw 3
Grille securing bracket 4
Note: Attach so that this surface is
the base of securing screws.
Screw 3
Grille securing bracket 4
●Readjust the height of the Multi-functional casement 1 with
the gauge which is attached to the grille as show right.
Note: It is recommended to make this adjustment before
installation of duct when fresh air intake.
Height adjustment
Attaching bracket for securing grille
●Use 8 screws 3 to secure the 4 Grille securing brackets 4 to each corner of Multi-functional casement 1.
(See the figure below.)
175