Engineering Manual

Figure
Specications
Remote Operation Adapter
PAC-SF40RM-E
Descriptions
Applicable Models
78-3/4 [2000]
6-5/16 [160]
5-18 [130]
1-3/16
[30]
1 [25]
13/16
[20]
2-3/4 [70]
19/32
[15]
Locally prepared cable
taking cut hole
Hole for wall
installation
(2 places)
Dimensions
Unit: inch [mm]
Material: ABS resin, Color: Gray (Munsell 3.07Y 6.16/0.33)
160 x 70 x 30
Weight
200g
Connecting cable
(indoor unit)
Indoor only
Temperature: 0 to 40 , Humidity: 35 to 85%RH (no condensation)
External dimensions (mm)
Supplied from indoor unit
Power
Exterior
5-wire (3 + 2) cable with connector (9-pin, 4-pin)
Operating conditions
Output signal
No-voltage "a" contact (relay contact method)
2 (Operation / Alarm)
Number of Contacts
Contact capacity
200V AC (30V DC)/1A or less
Minimum load
10mA
Input signal
Pulse signal (instantaneous non-voltage "a" contact), pulse width: 200ms or more
1 (start/stop)
Number of Contacts
Input/output
signal cable
Twisted: 0.5 to 1.25mm2, Single: Ø0.65 to Ø1.2mm
CV, CVS, or equivalent sheathed vinyl cord/cable
Type
Diameter
Distance
Output signal cable: Max. 100m
Input signal cable: Max. 10m (Extension relay must be used when exceeding 10m)
(locally prepared)
* This kit cannot be used with a wireless remote controller.
Water leakage alarm will not be displayed if the unit is built into the ceiling (PDH)
Extraction of non-voltage contact output.
*Use of optional [Remote Operation Adapter] and "remote display
panel" Part to be provided at your site) provides non-voltage con-
tact outputs of signals (operation, error) and operation/stop input
function.
Unable to use with wireless remote controller. (except for PKA-
RP·HAL/KAL)
SLZ-KA09/12/15NA
SEZ-KD09/12/15/18NA4
PLA-A12/18/24/30/36/42EA7
PEAD-A12/18/24/30/36/42AA7
PVA-A12/18/24/30/36/42AA7
273