Engineering Manual

How to Use / How to Install
Connector Cable for Remote Display
PAC-SA88HA-E/PAC-725AD-E
MULTIPLE REMOTE CONTROL DISPLAY
You can control several units with a multiple remote control display, by wir-
ing an optional multiple remote controller adapter (PAC-SA88HA-E) with
relays and lamps on the market.
How to wire
(1) Connect the multiple remote controller adapter to the connector CN51
on the indoor controller board.
(2) Wire three of the five wires from the multiple remote controller adapter
as shown in the figure below.
[Notes on Signs]
X1:Relay (for operation lamp)
X2:Relay (for check lamp)
RL:Operation Lamp
GL:Check Lamp
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple remote
controller adapter
The maximum distance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X2
X2
GL
RL
X1
X1
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unit No.2 unit No.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
X1-1
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
5
1
No.2 unit
5
1
No.3 unit
X1-2
X2-2
X1-3
X2-3
X2-1
X1-2
X1-3
X2-3
X2-2
[Field supplied parts]
Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.