Function Setting
Mode No.
( )RF thermostat
setup function No.
Initial setting
(Factorysetting)
23
(123)
11
(111)
Heater
control
Enable heater
basic control
1st
Heater OFF
Inlet air temp.
set temp
Heater ON
Inlet air temp.
set temp - 4.5°F(2.5°C)
•The fan will stop and the heater will turn off when [DEFROST] or [ERROR] is displayed.
1 -
Enable heater
comfort mode
1st
Heater OFF
Inlet air temp.
set temp
Heater ON
Inlet air temp.
set temp - 1.8°F(1°C)
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
2 1
2nd
Heater OFF
Inlet air temp.
set temp
Heater ON
Inlet air temp.
set temp - 2.7°F(1.5°C)
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
Enable heater
economy mode
1st
Heater OFF
Inlet air temp.
set temp - 1.8°F(1°C)
Heater ON
Inlet air temp.
set temp - 3.6°F(2°C)
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
2 2
1st: Heater output from CN24-1 (yellow) on the indoor unit control board.
2nd: Heater output from CN24-2 (Blue) on the indoor unit control board.