Engineering Manual

Multi-functional Casement PAC-SJ41TM-E
Electrical work of main unit
Temporary installation
●Fix the 2 screw with washer (black) 2 to each position.
(drain pipe corner position and to its opposite corner).
●Align the direction of the Multi-functional casement 1 according to the
label for checking the installation position attached inside the
Multi-functional casement 1.
Note: If installed in improper direction, parts damage, wind leakage,
or dew drop may result.
●Hook the hole of the Multi-functional casement 1 to the
screw with washer (black) 2 and hand tight.
Note: Be sure to use two persons for this work.
Fixing
Temporarily secure the 2 screws with washers 2, and
also the other 2 screws with washers 2, and then tighten
these screws with washers 2 after making sure that the position
of Multi-functional casement 1 is correct.
●Be sure to do the wiring (indoor/outdoor unit connection cable,
remote controller cable, etc.) before installing the Multi-functional
casement 1:
Note: Wiring after installing the Multi-functional casement 1 will be difficult.
Caution
Temporarily secure the 4 screws with washers.
Tightening the screws without temporarily securing
them could damage the screws with washers, or
cause air leakage.
Caution
When tightening the screw with washer 2, tighten it
at a torque of 2.8 to 3.6 N•m (2.1 to 2.6 ft•lbs) or less.
Never use an impact screwdriver.
It may result in parts damage.
Refrigerant pipe
Main unit
Drain pipe
Multi-functional
casement plates
(at 4 corners)
Note: The label for checking
installation position is
inside the Multi-functional
casement.
Screw with
washer 2
Screw with
washer 2
(Hand tightening)
Multi-functional
casement 1
3 Installation of Multi-functional casement
Multi-functional
casement 1
Ceiling
Main unit
The gap must be in a range from 17mm(11/16in.) to 22mm(7/8in.).
If out of range, it can cause malfunction.
Hole size on ceiling
(11/16 -7/8in.)
Gauge
(Insert to the Multi-functional casement)
17 mm
+5
0
Screw 3
Grille securing bracket 4
Screw 3
Grille securing bracket 4
Note: Attach so that this surface is
the base of securing screws.
Screw 3
Grille securing bracket 4
●Readjust the height of the Multi-functional casement 1 with
the gauge which is attached to the grille as show right.
Note: It is recommended to make this adjustment before
installation of duct when fresh air intake.
Height adjustment
Attaching bracket for securing grille
●Use 8 screws 3 to secure the 4 Grille securing brackets 4 to each corner of Multi-functional casement 1.
(See the figure below.)