Service Manual

3
OCH699
Outdoor unit model SUZ-KA09NA(H)2 SUZ-KA12NA(H)2 SUZ-KA15NA(H)2
Power supply V , phase , Hz 208/230 , 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 9 9 10
Fan motor F.L.A 0.50
Compressor
Model
KNB073FRVMC SNB092FQAMT SNB130FQBMT
R.L.A 6.2 6.6 7.4
L.R.A 7.7 8.2 9.3
Refrigeration oil oz(L)/
(Model)
9.1(0.27)/(FV50S) 11.8(0.35)/(FV50S) 11.8(0.35)/(FV50S)
Refrigerant control Linear expansion valve
Sound level
*
1
Cooling dB(A) 48 49 49
Heating dB(A) 50 51 51
Defrost method Reverse cycle
Dimensions
W in 31-1/2
D in 11-1/4
H in 21-5/8
Weight Ib 81
External nish Munsell 3Y 7.8/1.1
Control voltage
(by built-in transformer)
VDC 12 - 24
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in 1/4 (0.0315)
Gas in 3/8 (0.0315) 1/2 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor
& outdoor units
Height difference ft 40
Piping length ft 65
Refrigerant charge (R410A) 2 lb 5 oz 2 lb 9 oz
Note: Test conditions are based on AHRI 210/240.
Rating conditions (Cooling) — Indoor: 80˚F D.B., 67˚F W.B., Outdoor: 95˚F D.B., (75˚F W.B.)
(Heating) — Indoor: 70˚F D.B., 60˚F W.B., Outdoor: 47˚F D.B., 43˚F W.B.
3
SPECIFICATION
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Outdoor unit
208/230 V
1 phase
60 Hz
Min. 187
208 230 Max. 253