Indoor Service Manual

16 17
OCH669A
Continued to the next page
OPERATION
INDICATOR
lamp blinking
pattern
Beep Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 s
On
0.5 s
On
0.5 s
On
0.5 s
Off
Approx. 2.5 s
On
Approx. 3 s
On
0.5 s
On
0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1
st
2
nd
3
rd
1
st
2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
[Output pattern B]
[Output pattern A]
OPERATION
INDICATOR
lamp blinking
pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 s
On
0.5 s
On
0.5 s
On
0.5 s
On
0.5 s
Off
Approx. 2.5 s
On
0.5 s
On
0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates
the check code in the following table
n
th
1
st
2
nd
3
rd
1
st
2
nd
Self-check
starts
(Start signal
received)
Beeper sounds
Refer to the following tables for details on the check codes.
[Output pattern A] Errors detected by indoor unit
Wireless remote controller
Wired remote
controller
Symptom Remark
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1 P1 Intake sensor error
2 P2, P9 Pipe (liquid or 2-phase pipe) sensor error
3 E6, E7 Indoor/outdoor unit communication error
4 P4 Float switch connector open
5
P5 Drain pump error
PA Forced compressor error
6 P6
Freezing (during cooling operation)/Overheating protection operation (during
heating operation)
7 EE Assembly error (system error)
8 P8 Pipe temperature error
9 E4 Communication error between wired remote controller and indoor unit
10
11 PB(Pb) Indoor unit fan motor error
12 FB(Fb) Indoor unit control system error (memory error, etc.)
14 PL Refrigerant circuit abnormal
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Note: The supported check codes may vary depending on the connected outdoor unit.
Wireless remote controller
Wired remote
controller
Symptom Remark
Beeper sounds/OPERATION
INDICATOR lamp blinks
(Number of times)
Check code
1
E9 Indoor/outdoor unit communication error
For details, check the LED
display of the outdoor
controller board.
2
UP Compressor overcurrent interruption
3
U3, U4 Open/short of outdoor unit thermistors
4
UF Compressor overcurrent interruption (When compressor locked)
5
U2 Abnormal high discharging temperature/49C worked/insufcient refrigerant
6
U1, Ud Abnormal high pressure (63H worked)/Overheating protection operation
7
U5 Abnormal temperature of heat sink
8
U8 Outdoor unit fan protection stop
9
U6 Compressor overcurrent interruption/Abnormal of power module
10
U7 Abnormality of super heat due to low discharge temperature
11
U9, UH
Abnormality such as overvoltage or voltage shortage and abnormal synchro
-
nous signal to main circuit/Current sensor error
12
13
14
Others Other errors (Refer to the technical manual for the outdoor unit.)
Notes:
1. If the beeper does not sound again after the initial 2 beeps to conrm the self-check start signal was received and the OPERATION INDICATOR lamp does not
come on, there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to conrm the self-check start signal was received,
the specied refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.