(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Operation mode
Remarks
COOL HEAT
Intake temperature (TH1) 81°F [27°C] 69°F [20.5:]
Indoor uid pipe temperature (TH2) 41°F [5°C] 113°F [45:]
Indoor 2-phase pipe temperature (TH5) 41°F [5°C] 122°F [50:]
Set temperature 77°F [25°C] 72°F [22°C]
Outdoor liquid pipe temperature (TH3) 113°F [45°C] 41°F [5°C]
*1
Outdoor 2-phase pipe temperature (TH6) 122°F [50°C] 41°F [5°C]
*1
Outdoor air temperature (TH7) 95°F [35°C] 45°F [7°C]
*1
Outdoor suction (TH32) 41°F [5°C] 41°F [5°C]
*2
Temperature di󰀨erence code
(intake temperatureset temperature) (∆Tj)
5 5
Discharge super heat (SHd) 54°F [30°C] 54°F [30°C]
*2
Sub-cool (SC) 9°F [5°C] 9°F [5°C]
*2
*1
If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors to open/short.
And the unit runs emergency operation with the values listed above.
*2
If one thermistor is set to open/short, the values of SHd/SC will be different from the list above.
[Example] When liquid temperature thermistor (TH3) has an open or short circuit.
Thermistor COOL HEAT
TH3 113°F [45°C] 41°F [5°C]
TH6
Ta Tb
Regard normal gure as e󰀨ective data.
TH4
Tc Td
Regard normal gure as e󰀨ective data.
TH5 41°F [5°C] 122°F [50°C]
TH2 41°F [5°C] 113°F [45°C]
TH33 Regard normal gure as e󰀨ective data.
Discharge superheat (SHd)
Cooling = TH4−TH6 = Tc−Ta
Heating = TH4−TH5 = Td−122°F [50°C]
Degree of subcooling (SC)
Cooling = TH6−TH3 = Ta−113°F [45°C]
Heating = TH5−TH2 = 50°C−45°C = 5°C
or
= 122°F−113°F = F