Engineering Manual
How to Use / How to Install
Drain Socket PAC-SG61DS-E
1
Drain socket・・・・・・・・・・・1 pcs
2
Drain cap・・・・・・・・・・・・・5 pcs
3
Insulation part (for liquid pipe)・・・・1 pc
4
Insulation part (for gas pipe)・・・・・1 pc
5
Band・・・・・・・・・・・・・・・8 pcs
Make sure that the following parts are put in the package.
1
Accessory
Small size
Large size
(1) Glue the drain socket ① to the hole that is used to centralize the drainage among several
holes at the bottom of the unit with the glue (Prepare in the field).
(2) Glue the drain caps ② to close all the other unnecessary holes with the glue (Prepare in the field).
〈Note〉 Apply the glue securely, as the glue (Prepare in the field) will work as seal to prevent
water from leaking.
〈Note〉 Use the adhesive for the rubber and metal.
〈Recommended product〉 Supper X series made by CEMEDINE CO., Ltd.
(3) Insert a vinyl tube of which inner diameter 25 mm available commercially or a hard vinyl tube
VP25 to the drain socket ①.
2. Installation method for drain unit
Install the insulation parts to stop valve of the outdoor unit.
※The insulation parts should be installed after the tube has been connected to the unit.
※Some units are provided with a check valve near stop valve. In this case,
cut the insulation parts ③ and ④ so that they will fit the stop valve properly.
(1) Install the insulation part ③ with 2 holes to the liquid pipe side so that the holes
fit the valve caps and cover the stop valve entirely.
(2) Fix the insulation part ③ securely with bands ⑤.
Install the other insulation part ④ to the gas pipe side with the same procedure.
3. Installation method for insulation parts
・Cut both ends of the insulation
part ⑤ for gas tube side for the
model RP71 or less.
Cut the shaded portion
Caps
Stop valve
Tighten the bands
securely to completely
close the gap.
Cut the tip of the bands
after tightening.
③
⑤
①
②
Vinyl tube or hard vinyl tube (VP25)
☆Prepare the adhesive in the field.
298