Engineering Manual
Wired Remote Controller
PAR-32MAA
Table 3
Function
Setting No. of
SEZ,PEA PEAD MVZ,PVA
Mode No. 08 Mode No. 10
External static pressure
1
1
15 Pa
-
75 Pa
Vertical, Horizontal Left, Horizontal Right
External Static Pressure Setting
2 35 Pa 35 Pa 125 Pa
3 50 Pa 50 Pa 200 Pa
1
2
5 Pa 70 Pa 75 Pa
Down ow External Static Pressure Setting2
-
100 Pa 125 Pa
3
-
150 Pa 200 Pa
Table 4
MVZ, PVA
Function Setting
Mode No.
( )RF thermostat
setup function No.
Initial setting
(Factorysetting)
23
(123)
11
(111)
Heater
control
Enable heater
basic control
1st
Heater OFF
Inlet air temp.
set temp
Heater ON
Inlet air temp.
set temp - 4.5°F(2.5°C)
•The fan will stop and the heater will turn off when [DEFROST] or [ERROR] is displayed.
1
-
Enable heater
comfort mode
1st
Heater OFF
Inlet air temp.
set temp
Heater ON
Inlet air temp.
set temp - 1.8°F(1°C)
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
2 1
●
2nd
Heater OFF
Inlet air temp.
set temp
Heater ON
Inlet air temp.
set temp - 2.7°F(1.5°C)
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
Enable heater
economy mode
1st
Heater OFF
Inlet air temp.
set temp - 1.8°F(1°C)
Heater ON
Inlet air temp.
set temp - 3.6°F(2°C)
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
2 2
1st: Heater output from CN24-1 (yellow) on the indoor unit control board.
2nd: Heater output from CN24-2 (Blue) on the indoor unit control board.
219