Engineering Manual

2
Installation Diagram of the Drain lift up mechanism
Unit:mm
1 Confirming Supplied Accessories
* Before starting installation, make sure that the following accessories are present.
1
Drain lift up mechanism
2
Attachment
3
Screws (4×10)
4 VP-20 pipe
5
Pipe cover 6
Flexible hose 7
Fastener
8
L-shaped pipe (gas pipe)
9
L-shaped pipe (liquid pipe)
0
Insulator A
1
Insulator B
×1
1
Drain lift up
mechanism fixture
×1
For the installation of
drain lift up mechanism
×6
×1
For insulation of
VP20
pipe ×1
×1 ×1
×1
6t×220×80
(For internal insulation)
For the insulation of L-shaped
pipes and and the
refrigerant pipes.
×2
3t×250×120
(For external insulation)
For the insulation of L-shaped
pipes and and the
refrigerant pipes.
×2
* This drain lift up mechanism must be installed inside an indoor unit.
* Installing this drain lift up mechanism limits to arrange the refrigerant pipe only upward.
* To facilitate installation of the drain lift up mechanism, it should be installed before indoor unit.
* The size of the plumbing that must connect, by the refrigerant kind of the indoor unit that corresponds in the case of PAC-SH85DM-E, changes.
* Please refer to the installation manual of an indoor unit for details.
* The L-shaped pipes there are bringing are corresponding to either refrigerant plumbing.
W1 In case of accessory parts VP-20pipe
4
and pipe cover
5
do not have enough length because the lifting height is high, please supply locally.
PAC-SH84 ×1
L-shaped pipe
9
(liquid pipe
)
L-shaped pipe
8
(gas pipe
)
Drain lift up mechanism
1
Attachment
2
Fixing screw
3
Drainage plug
Drain connecting hole
Viewed from the Front
Fixing screw
3
Fixing screw 3
210
230
47
100
126
61
Elbow pipe
(locally supplied
)
VP-20pipe
(locally supplied
)
Fixing hole
VP-20pipe 4 W1
(outer diameter:
[
26
)
(pipe cover 5
)
W1
L-shaped pipe 8,9
(gas pipe, liquid pipe
)
Drain lift up
mechanism
1
Flexible hose 6
Max. 600
Viewed from the Right
Drain connecting hole on
the indoor unit
27
40
221
108.5
41
9
Rear side of the indoor unit
Right side of
the indoor
unit
Ceiling hole (2-
[
100
)
Knockout hole on the
indoor unit (for upper piping
)
Positions of Holes on the Ceiling
130
70
120
Viewed from the Top
<
Table 1
>
Gas pipe
Drain lift up mechanism Model
Liquid Pipe
[
15.88
[
9.52 PAC-SH84
112
73
134
Gas pipe
Right side panel
Flexible hose
6
Knockout hole on the indoor
unit(for upper piping)
Liquid pipe
Attachment
2
Drainage outlet
(for VP-20)
Drain lift up mechanism
1
How to Use / How to Install
Drain Pump PAC-SH84DM-E
191