Model Name Indoor Unit SEZ-KD09NA4 SEZ-KD12NA4 SEZ-KD15NA4 SEZ-KD18NA4
Cooling *1 Rated Capacity Btu/h 8,100 11,500 14,100 17,200
Heating at 47˚ F *2 Rated Capacity Btu/h 10,900 13,600 18,000 21,600
Power Supply Phase, Cycle, Voltage 1-Phase, 60Hz, 208 / 230V *4
Voltage
Indoor - Outdoor S1-S2 AC 208-230V
Indoor - Outdoor S2-S3 DC ±24V
MCA A 1.0
Fan
Blower Motor (ECM) F.L.A. 0.51 0.57 0.74
Airflow at Cooling/Heating
(Lo-Med-Hi)
CFM 194-247-317 247-317-388 353-441-529 423-529-635
External Static Pressure *3 In. W.G. 0.02-0.06-0.14-0.20
Sound Pressure Levels (Lo-Med-Hi) dB(A) 23-26-30 23-28-33 30-34-37 30-34-38
External Finish Galvanized-steel Sheets
Dimension
W: In. 31-1/8 39 46-7/8
D: In. 27-9/16
H: In. 7-7/8
Weight Lbs. 42 50 54 62
Drain-lift Mechanism (Included) H: In. 21-11/16
Field Drainpipe Size O.D. In. 1-1/4
Remote Controller Type
Select from PAC-WHS01WF-E for kumo cloud™, PAC-US444CN-1, MHK1, PAR-32MAA, or PAC-YT53CRAU Remote
Controllers
Refrigerant Type R410A
Refrigerant Pipe
Gas Side O.D.
In.
3/8 1/2
Liquid Side O.D. 1/4
Connection Method Flared/Flared
vvConnection Method Flared/Flared
NOTES: Test conditions are based on AHRI 210/240.
*1. Rating conditions (cooling)-Indoor: D.B. 80º F (26.7º C), W.B. 67º F (19.4º C); Outdoor: D.B. 95º F (35º C), W.B. 75º F (23.9º C).
*2. Rating conditions (heating)-Indoor: D.B. 70º F (21.1º C), W.B. 60º F (15.6º C); Outdoor: D.B. 47º F (8.3º C), W.B. 43º F (6.1º C).
*3. External static pressure is factory set to 0.06" W.G. Adjustable via remote controller.
*4. Indoor units receive power from outdoor units through field supplied interconnected wiring.
Specifications are subject to change without notice.
LIMITED WARRANTY I Five years parts and seven years compressor.
SEZ Ducted Indoor Unit
I
Heat Pump
(FOR MXZ-C OUTDOOR UNITS)
MITSUBISHI ELECTRIC / M-SERIES / SPECIFICATIONS / 43