Model Name
Indoor Unit SLZ-KA09NA SLZ-KA12NA SLZ-KA15NA
Outdoor Unit SUZ-KA09NA SUZ-KA12NA SUZ-KA15NA
Cooling *1
Rated Capacity Btu/h 8,400 11,100 15,000
Capacity Range Btu/h 3,100-10,900 3,400-13,300 3,800-17,700
Total Input W 700 920 1,460
Energy Efficiency SEER 15 15.4 16
Moisture Removal Pints/h 1.2 2.3 4.5
Sensible Heat Factor 0.84 0.77 0.67
Heating at 47° F *2
Rated Capacity Btu/h 10,900 13,600 18,000
Capacity Range Btu/h 3,100-14,100 3,100-17,100 3,100-22,000
Total Input W 930 1,180 1,950
HSPF (IV) Btu/h/W 9.6
Heating at 17° F *3
Rated Capacity Btu/h 6,200 8,300 10,200
Rated Total Input W 740 930 1,310
Maximum Capacity Btu/h 6,200 8,300 12,000
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208 / 230V *4
Voltage
Indoor - Outdoor S1 - S2 AC 208-230V
Indoor - Outdoor S2 - S3 DC ±24V
Indoor Unit
MCA A 1
Fan Motor (ECM) F.L.A. 0.23 0.28 0.28
Airflow at Cooling/Heating (Lo-Med-Hi)
DRY (CFM) 280-320-350 280-320-390 280-320-390
WET (CFM) 250-290-320 250-290-350 250-290-350
Sound Pressure Level dB(A) 29-32-38 30-34-39 31-35-40
External Finish Galvanized-Steel Sheets; Grille: Munsell 6.4Y 8.9/0.4
Dimension Unit (Grille)
W: In. 22-7/16 (25-5/8)
D: In. 22-7/16 (25-5/8)
H: In. 9-1/4 (13/16)
Weight Unit (Grille) Lbs. 36 (7)
Drain-lift Mechanism (Included) H: In. 19-11/16
Field Drainpipe Size O.D. In. 1-1/4
Remote Controller Type
Select from PAC-WHS01WF-E for kumo cloud™, PAC-US444CN-1, MHK1, PAR-32MAA, or PAC-
YT53CRAU Remote Controllers
Outdoor Unit
MCA A 12
MOCP A 15
Fan Motor (ECM) F.L.A. 0.50
Compressor
Model (Type) DC INVERTER-driven DC INVERTER-driven Twin Rotary
R.L.A. 6.6 7.4
L.R.A. 8.2 9.3
Airflow (Cooling/Heating) CFM 1,151/1,225 1,229/1,172 1,243/1,229
Refrigerant Control Linear Expansion Valve
Defrost Method Reverse Cycle
Sound Pressure Level at Cooling *1 dB(A) 46 49
Sound Pressure Level at Heating *2 dB(A) 50 51
External Finish Color Munsell No. 3Y 7.8/1.1
Dimensions
W: In. 31-1/2
D: In. 11-1/4
H: In. 21-5/8
Weight Lbs. 66 77 80
Refrigerant
Type R410A
Charge Lbs., Oz. 2 2, 9
Oil Type (fl. oz.) NEO22 (10.8) NEO22 (15.2)
Refrigerant Pipe
Gas Side O.D. In. 3/8 1/2
Liquid Side O.D. In. 1/4
Refrigerant Pipe Length
Height Difference (Max.) Ft. 40
Length (Max.) Ft. 65
Connection Method Indoor/Outdoor Flared/Flared
SINGLE-ZONE
I
SLZ System
I
Heat Pump
NOTES: Test conditions are based on AHRI 210/240.
*1. Rating conditions (cooling)-Indoor: D.B. 80º F (27º C), W.B. 67º F (19º C);
Outdoor: D.B. 95º F (35º C), W.B. 75º F (24º C).
*2. Rating conditions (heating)-Indoor: D.B. 70º F (21º C), W.B. 60º F (16º C);
Outdoor: D.B. 47º F (8º C), W.B. 43º F (6º C).
*3. Rating conditions (heating)-Indoor: D.B. 70º F (21º C), W.B. 60º F (16º C);
Outdoor: D.B. 17º F (-8º C), W.B. 15º F (-9º C).
*4. Indoor units receive power from outdoor units through field-supplied interconnected wiring.
Note: ESP at 208/230V, 60 Hz. See manual for Static Performance Curve, including at 0.02 in W.G.
Specifications are subject to change without notice.
LIMITED WARRANTY I Five years parts and seven years compressor.
38 / MITSUBISHI ELECTRIC / M-SERIES / SPECIFICATIONS