Service Manual

68
OCH636B
Brief Check of POWER MODULE
If they are short-circuited, it means that they are broken.
Measure the resistance in the following points (connectors, etc.).
1. Check POWER MODULE
1 Check of DIODE circuit
R
P1 S P1 R N1 S N1
2 Check of IGBT circuit
P2
L1 P2 L2 N2 L1 N2 L2
3 Check of INVERTER circuit
P3
U , P3 V , P3 W , N3 U , N3 V , N3 W
Note: The marks
R , S , L1 , L2 , P1 , N1 , U , V and W
show in the diagram are not actually printed on the board.
CN6
Thermistor
CN4
Connect to the outdoor
controller circuit board
(CN4)
NI, LI
Voltage of 230 V AC is input
(Connected to the terminal block
(TB1))
EI,E2,E3,E4
Connected to
the ground
CNDC
280–380 V DC (1+, 3–)
connect to the outdoor
controller circuit board
(CNDC)
TB1A, TB3A, TB1B, TB3B
Connected to DCL
CNAC1, CNAC2
230 V AC
Connected to the outdoor
controller circuit board
(CNAC)
CN2
Connect to the outdoor controller circuit board (CN2)
15: Transmitting signal to outdoor controller
circuit board (0–5 V DC)
25: Zero cross signal
(0–5 V DC)
3,4: 16 V DC
65: 16 V DC
75: 16 V DC
P3
U
V
W
N3
P2
L1
L2
N2
S
R
P1
N1
Outdoor power circuit board
PUZ-A24NHA7
PUZ-A30NHA7
PUZ-A24NHA7-BS
PUZ-A30NHA7-BS
PUY-A24NHA7
PUY-A30NHA7
PUY-A24NHA7-BS
PUY-A30NHA7-BS