Service Manual

53
OCH636B
10-6-1. Check method of outdoor controller circuit board
PUZ-A12NKA7 PUZ-A18NKA7 PUY-A12NKA7 PUY-A18NKA7
PUZ-A12NKA7-BS PUZ-A18NKA7-BS PUY-A12NKA7-BS PUY-A18NKA7-BS
PUZ only
Did the fuse (F1 and F2) blow?
PTC1 or PTC2 = open ?
PNC board check
Outdoor controller circuit board
Is the voltage of main incoming
power 198–253 V AC?
Is the voltage of bus bar voltage
(between DS1 "+" and "")
280–350 V DC?
Check the breaker and power supply.
Turn off the incoming power supply and
check the resistance of PTC1and PTC2 on
the PNC board.
• Replace the PNC board.
• Check wiring.
Replace the PNC board.
Check the indoor controller board wiring.
Did the fuse (F3 and F4) blow?
Check the wiring for 21S4.
Is the voltage of the compressor
(U-V,U-W and V-W) balanced?
• Check model setting switch.
• Check wiring.
Normal
ACL
TB1
208/230 V AC
±
10%
L2
L1
U
V
W
U–V 10–200 V AC
V–W 10–200 V AC
W–U 10–200 V AC
Comp
PTC1, PTC2
Yes
Yes
Yes (blow)
Yes (blow)
Yes
Yes
No
No
No
No
No
No