Engineering Manual

PAC-SH91MK-E/PAR-SA92MW-E/PAR-SL93B-E
Pair Number Setting
Pair Number Setting
• This is the setting to specify the unit to operate with the wireless remote controller.
• Make setting for J41, J42 (Jumper wire) of indoor controller board and the pair number of wireless remote controller.
• The pair number setting is available with the 4 patterns as shown in the following table. Make setting for the pair
number (J41, J42) of indoor controller board and the pair number of wireless remote controller which is used
as shown in the following table. *The initial setting is Pair No. “0”.
A Pair No. of wireless remote controller
Indoor PC board
Initial setting
Cut J41
Cut J42
Cut J41, J42
0
1
2
3 ~ 9
1 Press the SET button with something sharp at the end.
Start this operation from the status of remote controller display turned off.
MODEL SELECT blinks and Model No. is lighted.
2 Press the button twice continuously. Pair No. “0” blinks.
3 Press the temp button to set the pair number you want to set.
4 Press the SET button with something sharp at the end.
Set pair number is lighted for 3 seconds then turned off.
min
CN6Y CN4Y CN90
Jumper wire (J41, J42)
* The positions of the connectors may be different according to the model.
Please refer to the wiring diagram to confirm the positions of the connectors.
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL
SELECT
NOT AVAILABLE
SWING
CHECK
FAN
TEST
RUN
°F
°C
AMPMSTOP
START
AMPM
COOL
DRY
AUTO
FAN
HEAT
1 4
1
4
2
3
3
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
A
3
2
1
4
2
Function Selection of Wireless Remote Controller
4
• Temperature display °C/°F setting (Change of temp mode from °F to °C)
1 Press the set button with something sharp at the end. MODEL SELECT blinks.
2 Press the button. “F:” blinks.
3 Press the button. “C:” blinks.
4 Press the SET button with something sharp at the end.
MODEL SELECT is lighted for three seconds, then turned off.
AUTO START
Test Run
5
Measure an impedance between the power supply terminal block on the outdoor unit
and the ground with a 500V Megger and check that it is equal to or greater than 1.0 M".
1 Turn on the main power to the unit.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display turned off.)
A TEST RUN and current operation mode are displayed.
3 Press the ( ) button to activate COOL mode, then check whether
cool air is blown out from the unit.
4 Press the ( ) button to activate HEAT mode, then check whether
warm air is blown out from the unit.
5 Press the button and check whether strong air is blown out from the unit.
6 Press the button and check whether the auto vane operates properly.
7 Press the ON/OFF button to stop the test run.
TEST RUN
MODE
MODE
FAN
VANE
NOTE : • Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.
• It is not possible to run in FAN, DRY or AUTO mode.
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
NOT AVAILABLE
SWING
TEST
RUN
COOL
3
4
6
5
7
2
A
3
Function Selection of Wireless Remote Controller
Test Run
262