Engineering Manual

244
Simple MA Remote Controller
PAC-YT53CRAU
Set the functions of each indoor unit from the remote controller, as required. The functions of each
indoor unit can be selected only from the remote controller.
Set the functions by selecting the necessary items from Table 1.
Table1. Function selection contents
(For a detailed description of the factory settings and mode of each indoor unit, refer to the indoor unit installation manual.)
* Static pressure setting can be made by using Mode 08 in combination with Mode 10 depending on
the indoor unit model. Refer to the Indoor unit Installation Manual for details.
* For mode numbers other than listed above, refer to the indoor unit installation manual.
7 Function Selection for M-Series and P-Series
Mode
No.
sgnitteSedoM
Setting
No.
Check Unit numbers
01 Automatic recovery
after power failure
.rebmun tinU eht rof "00" teS1elbasiD
These settings apply to all the
connected indoor units.
Enable (Four minutes of standby time is required
after the restoration of power.)
2
02 Thermistor selection
(Indoor temperature
detection)
Average temperature reading of the indoor units
in operation
1
Thermistor on the indoor unit to which the remote
controller is connected (fixed)
2
Built-in sensor on the remote controller 3
1detcennoc toNnoitcennoc YANSSOL30
Connected (without outdoor air intake by the
indoor units )
2
Connected (with outdoor air intake by the indoor
units )
3
1V 042egatlov rewoP40
2V 032 ,V 022
05 AUTO mode Enable (Automatically the unit achieves effective
energy saving operation.)
1
2elbasiD
eht rof LA ro 40 ot 10" teS1sruoh 001ngis retliF70
Unit number.
These settings apply to each
indoor unit.
If "01” (“02”, “03”, “04") is
set for the Unit number, the
settings apply only to the
specified indoor unit
regardless of the number of
connected indoor units (one
through four units).
If "AL" is set for the Unit
number, the settings apply
to all the connected indoor
units regardless of the
number of connected
indoor units (one through
four units).
2sruoh 0052
3deyalpsid toN
1)dradnats ro( edom tneliSdeeps naF80
2)1 gniliec hgiH ro( dradnatS
3)2 gniliec hgiH ro( gniliec hgiH
1lanoitcerid 4steltuo ria fo .oN90
2lanoitcerid 3
3lanoitcerid 2
1oNsnoitpo dellatsnI01
(High performance filter)
2seY
11 Vane setting No vanes (or the vane setting No.3 is effective.) 1
Equipped with vanes
(The vane setting No.1 is effective.)
2
Equipped with vanes
(The vane setting No.2 is effective.)
3
Make the following settings for M-Series and P-Series if necessary.
(This setting cannot be made with CITY MULTI Control System. To make CITY MULTI indoor
). noitces ot refer ,rellortnoc etomer eht morf sgnittes tinu
9 Function Selection for CITY MULTI
NOTE: When the indoor unit functions were changed using the function selection after
installation is complete, always indicate the set contents by entering check marks or
other marks in the appropriate check field of Table 1.