Engineering Manual
Wired Remote Controller
PAR-32MAA
Table 2
Function Settings
Mode
No.
Setting
No.
Initialsetting(Factorysetting)-:Notgavailable
4waycasette
Ceiling
suspended
Wall mounted
PLA-EA
SLZ-KA•NA
PCA-KA PKA-HA PKA-KA
Filter sign
100Hr
07
(107)
1
● ●
2500Hr 2
● ● ●
No lter sign indicator 3
Air ow
(fan speed)
Quiet
08
(108)
1
- -
Standard 2
●
-
● ● ●
Hi ceiling 3
-
-
No. of air outlets
4 directions
09
(109)
1
●
- - - -
3 directions 2
- - - -
2 directions 3
- - - -
Installed options
(High performance lter)
Not supported
10
(110)
1
●
-
●
- -
Supported 2
- - -
Horizontal vane
setting
No vanes (Vane No.3 setting: PLA only)
11
(111)
1
- - -
Vane No.1 setting 2
-
●
- -
Vane No.2 setting 3
●
- - -
Vane differential setting
in heating mode (cold
wind prevention)
Low (24C-28C)
14
(114)
1
Standard (28C-32C) 2
● ● ● ● ●
High (35C-38C) 3
Vane Swing
Not supported (Swing: PLA only)
23
(123)
1
Supported (Wave airow: PLA only) 2
● ● ● ● ●
Setting temperature
in heating (4 deg
up)*1PKA: 2 deg up
Available
24
(124)
1
● ● ● ● ●
Not available 2
Fan speed during the
heating thermostat is
OFF
Extra low
25
(125)
1
● ● ● ● ●
Stop 2
Setting fan speed 3
Fan speed during the
cooling thermostat is
OFF
Setting fan speed
27
(127)
1
● ● ● ● ●
Stop 2
Detection of abnormality
of the pipe temperature
(P8)
Available
28
(128)
1
● ● ● ● ●
Not available 2
( )RF thermostat setup function No.
Function Settings
Mode
No.
Setting
No.
Initialsetting(Factorysetting)-:Notgavailable
Ceiling concealed Multi position
SEZ-KD•NA
PEA-AA
PEAD-AA4 PEAD-AA5
MVZ PVA
Filter sign
100Hr
07
(107)
1
2500Hr 2
No lter sign indicator 3
● ● ● ● ● ●
External static pressure
setting
*Refer to Table 3
08
(108)
1
● ●
2
● ●
3
● ●
10
(110)
1
● ● ● ● ● ●
2
Heater control *Refer to Table 4
11
(111)
1
- - -
● ● ●
2
- - -
23
(123)
1
● ● ● ●
2
● ●
Setting temperature in
heating
(4 deg up)
Available
24
(124)
1
● ● ● ● ● ●
Not available 2
Humidier
Not supported
13
(113)
1
- - - -
Supported 2
- - - -
● ●
Fan speed during the
heating thermostat is
OFF
Extra low
1
25
(125)
1
● ● ● ● ● ●
Stop 1 2
Setting fan speed
1 3
Fan speed during the
cooling thermostat is
OFF
Setting fan speed
27
(127)
1
● ● ● ● ● ●
Stop 2
Detection of abnormality
of the pipe temperature
(P8)
Available
28
(128)
1
● ● ●
Not available 2
● ● ●
1 High speed setting depending on heater control.
( )RF thermostat setup function No.