Engineering Manual

16
NOTES : *1.Rating conditions (cooling)-Indoor : D.B. 26.7°C(80°F), W.B. 19.4°C(67°F) Outdoor : D.B. 35°C(95°F), W.B. 23.9°C(75°F)
(heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. 8.3°C(47°F), W.B. 6.1°C(43°F)
*2.Conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -8.3°C(17°F), W.B. -9.4°C(15°F)
*3.Conditions (heating)-Indoor : D.B. 21.1°C(70°F), W.B. 15.6°C(60°F) Outdoor : D.B. -15°C(5°F), W.B. -15°C(5°F)
Operating range
Indoor intake air temperature
D.B. 32°C(90°F), W.B. 23°C(73°F)
Outdoor intake air temperature
D.B. 46°C(115°F)
Cooling
Heating
Maximum
Maximum
Minimum
Minimum
* In case that the wind baffle is installed. (In case that the wind baffle is not installed, the minimum temperature will be -5°C(23°F)DB.)
D.B. 19°C(66°F), W.B. 15°C(59°F)
D.B. 28°C(83°F)
D.B. 10°C(50°F)
D.B. -5°C(23°F)
D.B. -18°C(0°F)*
D.B. -25°C(-13°F), W.B. -25°C(-13°F)
D.B. 21.1°C(70°F), W.B. 15°C(59°F)
Model name Indoor unit PCA-A30KA7 PCA-A36KA7 PCA-A42KA7
Outdoor unit PUZ-HA30NHA5 PUZ-HA36NHA5 PUZ-HA42NKA
Cooling Max. Capacity Btu/h 30,000 36,000 42,000
Rated Capacity Btu/h 30,000 34,000 42,000
Min. Capacity Btu/h 18,000 18,000 19,000
Total Input W 2,480 2,810 4,200
EER Btu/h/W 12.1 12.1 10.0
SEER Btu/h/W 16.1 16.6 14.5
Moisture Removal Pints/h 8.3 8.2 11.7
SHF 0.69 0.73 0.69
*1 Power factor % 96.3 93.3 95.6
Heating Max. Capacity Btu/h 34,000 40,000 54,000
Rated Capacity Btu/h 32,000 38,000 48,000
Min. Capacity Btu/h 18,000 18,000 21,000
Total Input W 2,990 3,270 4,150
COP W/W 3.14 3.41 3.39
HSPF (IV/V) Btu/h/W 9.3/7.2 10.3/8.2 10.4/9.0
*1 Power factor % 96.3 94.2 95.5
Heating at 17°F
(-8.3°C)
Max. Capacity Btu/h 32,000 38,000 48,000
Total Input W 5,170 5,720 7,020
*2 COP W/W 1.81 1.95 2.00
Heating at 5°F
(-15°C)
Max. Capacity Btu/h 32,000 38,000 48,000
Total Input W 5,830 6,550 7,580
*3 COP W/W 1.61 1.70 1.85
Power supply Phase, Cycle, Voltage 1phase, 60Hz, 208/230V
Breaker size A 30 40
Voltage Indoor - Outdoor S1-S2 AC208/230V
Indoor - Outdoor S2-S3 DC24V
Indoor - Remote Controller DC12V
Indoor unit MCA A 1 2
MOCP A 15
Fan motor F.L.A. 0.54 0.97
Fan motor output W 95 160
Air ow DRY(Lo-M2-M1-Hi) CMM 16.0-17.0-18.0-20.0 22.0-24.0-26.0-28.0 23.0-25.0-27.0-29.0
Air ow WET(Lo-M2-M1-Hi) CMM 15.0-16.0-17.0-19.0 20.0-22.0-24.0-26.0 21.0-23.0-25.0-27.0
Air ow DRY(Lo-M2-M1-Hi) CFM 565-600-635-705 775-850-920-990 810-885-955-1,025
Air ow WET(Lo-M2-M1-Hi) CFM 530-565-600-670 705-775-850-920 740-810-885-955
External pressure in.WG [Pa] 0
Sound level
(Lo-M2-M1-Hi)
dB(A) 35-37-39-41 37-39-41-43 39-41-43-45
External nish White Munsell 6.4Y 8.9/0.4
Dimension Unit W: mm [inch] 1,280 [50-3/8] 1,600 [63]
D: mm [inch] 680 [26-3/4]
H: mm [inch] 230 [9-1/16]
Weight Unit kg[lbs] 32 [71] 36 [79] 39[86]
Field drain pipe size O.D. mm[inch] 26 [1-1/32]
Remote Controller Attached in indoor unit
Outdoor unit MCA A 28 37
MOCP A 40 44
Fan motor F.L.A. 0.4 + 0.4
Fan motor output W 86 + 86
Compressor Type ANB33FJEMT ANB42FJTMT
R.L.A. 18.0 19.0
L.R.A. 27.5 28.0
Air ow CMM [CFM] 100 [3,530] 94 [3,320]
Refrigerant Control Electronic Expansion Valve
Defrost Method Reverse cycle
Sound level at cooling dB(A) 52 49
Sound level at heating dB(A) 53 51
External nish Munsell 3Y 7.8/1.1
Dimension Unit W: mm [inch] 950 [37-3/8] 1,050 [41-6/16]
D: mm [inch] 300+30 [13 + 1-3/16]
H: mm [inch] 1,350 [53-1/8] 1,338 [52-11/16]
Weight Unit kg[lbs] 120 [265] 130 [287]
Refrigerant Type R410A
Charge kg [lbs,oz] 5.5 [12lbs 2oz] 6.0 [13lbs 4oz]
Oil L [oz] 1.4(FV50S) [45] 1.7(FVC68D) [54]
Refrigerant pipe
size
Gas side O.D. mm [inch] 15.88 [5/8]
Liquid side O.D. mm [inch] 9.52 [3/8]
Refrigerant pipe
length
Height difference IU-OU Max. 30m [Max.100ft]
Length Max. 75m [Max.245ft]
Refrigerant Piping Not Supplied
Connection Method Flared