Specifications

15
High sound-
absorbing rooms
Broadcasting
studio, music
room, etc.
3 to 7 dB
Normal rooms
Reception room,
hotel lobby, etc.
6 to 10 dB
Low sound-
absorbing rooms
Office, hotel
room
9 to 13 dB
Location
examples
Noise levels
Having trouble?
Air conditioner operates without the ON/OFF button being pressed.
Air conditioner stops without the ON/OFF button being pressed.
Remote controller timer operation cannot be set.
“PLEASE WAIT” appears in the remote controller display.
An error code appears in the remote controller display.
Draining water or motor rotation sound is heard.
Noise is louder than specifications.
Here is the solution. (Unit is operating normally.)
Is the on timer set?
Press the ON/OFF button to stop operation.
Is the air conditioner connected to a central remote controller?
Consult the concerned people who control the air conditioner.
Does “ ” appear in the remote controller display?
Consult the concerned people who control the air conditioner.
Has the auto recovery feature from power failures been set?
Press the ON/OFF button to stop operation.
Is the off timer set?
Press the ON/OFF button to restart operation.
Is the air conditioner connected to a central remote controller?
Consult the concerned people who control the air conditioner.
Does “ ” appear in the remote controller display?
Consult the concerned people who control the air conditioner.
Are timer settings invalid?
If the timer can be set,
WEEKLY
,
SIMPLE
, or
AUTO OFF
appears in
the remote controller display.
The initial settings are being performed. Wait approximately 3 minutes.
The protection devices have operated to protect the air conditioner.
Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be sure
to provide the dealer with the model name and information that appeared
in the remote controller display.
When cooling operation stops, the drain pump operates and then stops.
Wait approximately 3 minutes.
The indoor operation sound level is affected by the acoustics of the par-
ticular room as shown in the following table and will be higher than the
noise specification, which was measured in an echo-free room.
10. Trouble Shooting
11. Specifications
Model
Power source (voltage <V>/Frequency <Hz>)
Rated Input (Indoor only) <kW>
Rated Current (Indoor only) <A>
HEATER <kW>
Dimension (Height) <mm>
Dimension (Width) <mm>
Dimension (Depth) <mm>
Fan airflow rate (Low-High) <m
3
/min>
External static pressure <Pa>
Noise level (Low-High) <dB>
Net weight <kg>
PEA-RP71EA PEA-RP100EA PEA-RP125EA PEA-RP140EA
~/N 230/50
0.39/0.39 0.44/0.44 0.65/0.65 1.08/1.08
1.66/1.66 1.87/1.87 2.76/2.76 4.55/4.55
––––
428
785 1055 1255 1415
690
22-27 27-34 34-42 48-60
125
52-55 54-58 51-55
46 58 72 73
Operating range
Indoor air intake temperature Outdoor air intake temperature
Cooling
Maximum 35 °C DB, 22.5 °C WB 46 °C DB
Minimum 19 °C DB, 15 °C WB 5 °C DB *1
Heating
Maximum 28 °C DB 21 °C DB, 15 °C WB
Minimum 17 °C DB 11 °C DB, 12 °C WB *2
*1. If optional Air protect guide installed D.B. 15 °C.
*2. For 100-250 models D.B. 20 °C, W.B. 20 °C.