Specifications
86
SW2 setting
1
ON
23456
Display detail
Explanation for display Unit
Indoor setting temperature
17~30
:
1
ON
23456
1
ON
23456
1
ON
23456
1
ON
23456
Outdoor piping temperature/Cond./Eva.
(TH6)
– 39~88
Discharge super heat. SHd
0~255
Cool = TH4-TH6
Heat = TH4-TH5
Communication demanded capacity.
0~255
When no communication demanded
setting, “100” is displayed.
– 39~88
(When the temperature is 0: or less, “–” and
temperature are displayed by turns)
:
:
:
%
0~255
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) 115 :
One second interval.
1 15
0~255
(When the capacity is 100 or more, the hundreds
digit and tens, units digit are displayed by turns)
(Example) When 100
One second interval.
1 00
1
ON
23456
Code
Error thermistor display
3: Outdoor liquid piping thermistor (TH3)
6: Outdoor condenser thermistor (TH6)
1
ON
23456
17~30
Sub cool. SC
0~130
Cool = TH6-TH3
Heat = TH5-TH2
0~130
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
Step
Fan step on error occurring.
0~16
0~16
1
ON
23456
LEV opening on error occurring
0~440
Display by scaled 1/5 to actual opening
1
ON
23456
:
1
ON
23456
:
0~440
(When the pulse is 100 or more, the hundreds digit
and tens, units digit are displayed by turns)
(Example) When the display shows 300.
300 ✕ 5 = 1500 pulse
Pulse
– 39~88
(When the thermistor is 0:and less, “–” and
temperature are displayed by turns.)
(Example) When –15:
One second interval
– 15
Outdoor piping temperature/Cond./Eva.
on error occurring. (TH6)
– 39~88
Discharge super heat on error occurring.
SHd
0~255
Cool = TH4-TH6
Heat = TH4-TH5
0~255
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 150:
One second interval
1 50
1
ON
23456
:
0~130
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 115:
One second interval
1 15
Sub cool on error occurring. SC
0~130
Cool = TH6-TH3
Heat = TH5-TH2
When no error thermistor, “–” is
displayed.
When air conditioners are
connected to M-NET and
under central control.