Specifications

84
SW2 setting
1
ON
23456
Display detail
Explanation for display Unit
Piping temperature (TH3) on error
occurring
– 40~90
– 40~90
(When the coil thermistor is 0:and less, “–” and
temperature are displayed by turns)
(Example) When –15:
One second interval
15
:
1
ON
23456
1
ON
23456
1
ON
23456
1
ON
23456
Compressor temperature (TH4) or
discharge temperature (TH4) on error
occurring.
0~216
Compressor operating current on error
occurring.
0~40
Error code history (1) (latest)
Alternate display of abnormal unit
number and code.
Error code history (2)
Alternate display of error unit number
and code.
0~216
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 130:
One second interval
1 30
:
A
Code
display
Code
display
0~40
When no error history,
“ 0 ” and “– –” and displayed by turns.
When no error history,
“ 0 ” and “– –” and displayed by turns.
1
ON
23456
1
ON
23456
Thermistor ON time .
0~999
Trial run elapsed time.
0~120
0~999
(When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 245 minutes
One second interval
2 45
0~120
(When the time is 100 or more, the hundreds digit
and tens, units digit are displayed by turns.)
(Example) When 105 minutes
One second interval
1 05
Minute
Minute
Unit
The number of connected indoor unit.
0~4
0~4
OCT03-E-3.qxp 04.3.26 1:50 PM Page 84