Specifications

65
3
2
1
3
2
1
Control modes
Control details
3-1. Drain pump control
•Always drain pump ON during the COOL and DRY mode operation.
(Regardless of the compressor ON/ OFF)
•When the operation mode has changed from the COOL or DRY to the others
(including Stop), OFF the control after the drain pump ON for 3 minutes.
Drain sensor function
• Energize drain sensor at a fixed voltage for a fixed duration. After energizing,
compare the drain sensor’s temperature to the one before energizing, and judge
whether the sensor is in the air or in the water.
Basic control system
• While drain pump is turned on, repeat the following control system and judge
whether the sensor is in the air or in the water.
•Drain sensor temperature rise (t)
•Temperature of drain sensor before current is applied (T0)
•Temperature of drain sensor after current is applied (T
1)
[ t = T1T0 ]
(1)Initial setting : Start at COOL mode and horizontal vane.
(2)Vane position : Horizontal Downward A Downward B Downward CSwing
(3)Detecting position (AC 200-240V timing motor)
Positioning the each vane as a basic position (horizontal or shutter) the starting
OFF ON of the limited switch. When the basic position is not able to detect for
10 minutes, the vane will be stopped at that time. (vane swing motion for 10
minutes)
(4)Restriction of the downward vane setting
When setting the downward vane A, B and C in [Mid2] or [Low] of the fan speed
notch, the vane changes to horizontal position after 1 hour have passed.
4. Vane
(up/ down vane change)
By the remote controller setting
wModel which is
installed louver
function.
5. Louver
(Left / right change)
3. Drain pump
Remarks
1 Drain sensor
Indoor controller
board
CN31
2 If the unit is
without the
drain sensor,
install the
jumper
connector.
Indoor controller
board
CN31
When installing
the jumper
connector,
determine to
detect
compulsorily in
the air.
1 Whether the
unit has a swing
function is listed
in the function/
control specifications.
2 See the
function/control
specifications for
the vane motor
type.
3
"SET FOR 1 HOUR"
appears on the
wired remote
controller.
Timing of
energizing
drain sensor
ON
OFF
Stand by for
a minute
30 sec.
Detect the
temperature
before
energizing
(T0)
Detect the
temperature
after
energizing
(T1)
Judge whether
the sensor is in
the air or in the
water.
30 sec.Stand by for
a minute
·······Repeat