Specifications

59
(2) The transmitting specification for “A” control
1Wiring regulations
Cross section
of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
(50)
2
(45)
3
60
4
Not
applicable
5
Flat
1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.
2 : In case that cable with stripe of yellow and green is available.
3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
2
.
4 : In case of regular polarity connection (S1-S2-S3).
5 : In the flat cables are connected as this picture, they can be used up to 80m.
6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
Flat
Round
Wire size
(mm
2
)
Number
of wires
Clockwise : S1-S2-S3
w Pay attention to stripe of yellow and green
Clockwise : S1-S2-S3-Open
w Connect S1 and S3 to the opposite angle
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
Polarity
L(m)
6
(3C Flat cable 2)
S1 S2 S3
Section Communications from remote controllers
Communications between indoor and outdoor units
The maximum length of
total wiring
500m 80m (50m for the wirings between indoor and
outdoor units; 30m for the wirings among indoor
units)
The maximum numbers
for connection
One remote controller can connect and operate
up to 16 indoor units by grouping them.
1
One group can connect up to two remote con-
trollers.
2
1 Remote controller considers multiplex units as
a single group.
2 PSA-JGA should be excluded.
One outdoor unit can connect up to four indoor
units.
The cables applicable 0.3mm
2
to 1.25mm
2
Use either VVF flat-type cable (3 cores:
{1.6mm or more) or wires in the table below.
3 The diameter of the cables depends on
each unit.
Others The wirings as follows are not allowed:
• The wiring that the indoor units of the same
refrigerant system are connected through TB5.
• The wiring which directly connects the terminals
for remote controllers.
The core wire connected to terminal S2 shall be
placed at the center of VVF flat-type cable.
Section Communications from remote controllers
Communications between indoor and outdoor units
Transmitting speed 83.3 bit/sec. (1 bit = 12ms) 83.3 bit/sec. (1 bit = 12ms)
Normal transmission The terminal for remote controller transmits sig-
nals every 7.5 seconds; the indoor unit whose
refrigerant address is “0” responds them.
Outdoor unit transmits signals every 3 seconds;
all the connected indoor units respond them.
Modulation The waveform modulates at 50kHz. There is no modulation.
Detection of abnormal
communication
When transmitting error is detected for three con-
secutive minutes.
When transmitting error is detected for three
consecutive minute.
2Transmitting specification
WIRING SPECIFICATIONS FOR 220~240V 50Hz
(INDOOR-OUTDOOR CONNECTING CABLE)
PU(H)-P1.6VGA~P6YGA
PU(H)-P1VGAA.UK~P6YGAA(.UK)
(Except PUH-8YE,PUH-10YE)