Specifications
46
66
PKH-P2.5, P3, P4FALH
PKA-P2.5, P3, P4FAL
PKA-P2.5, P3, P4FAL-H
1
1
2
2
3
3
Red
White
Black
Relay connector
4
5
2
361
Orange
Red
Pink
Yellow Brown Blue
M
Parts name Check points
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Fan motor
107"
Measure the resistance between the terminals using a tester.
Contactor
(for heater)
(Only P2.5~P4FALH)
Abnormal
Open or short
10 11
88H
Normal
P2.5, P3, P4
Abnormal
Open or short
Red–Black
White–Black
Motor terminal
or
Relay connector
P2.5, P3
99.5"
103.9"
P4
62.6"
74.0"
Normal
Open or short
Abnormal
Brown–Yellow
Brown–Blue
Red–Orange
Red–Pink
Connector
Normal
P2.5, P3, P4
186~214"
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Vane motor
Measure the resistance of each heater element by using a tester.
Heater
(Only P2.5~P4FALH)
Normal
Abnormal
P2.5, P3
18.9"
700W 240V
P4
16.5"
800W 240V
Open or short
Protector
OFF:130i5:
ON :80i20:
OCT03-E-2.qxp 04.3.26 1:48 PM Page 46