Specifications

43
22
PLH-P1.6, P2, P2.5, P3, P4, P5, P6KAH
PLA-P1.6, P2, P2.5, P3, P4, P5, P6KA
PLA-P1.6, P2, P2.5KA1
PLH-P1.6, P2, P2.5KAH.UK
PLA-P1.6, P2, P2.5KA.UK
1
1
2
2
3
3
Red
White
Black
Relay connector
1
2
Red
Red
Parts name Check points
Measure the resistance between the terminals using a tester.
(Winding temperature 20:)
Measure the resistance between the terminals using a tester.
(Winding temperature 20:~30:)
Drain-up
mechanism
Fan motor
Abnormal
Open or short
Normal
327k"
107"
Measure the resistance between the terminals using a tester.
Contactor
(for heater)
(Only P·KAH type)
Abnormal
Open or short
10 11
88H
Normal
P1.6~P6
Abnormal
Open or short
Red–Black
White–Black
Motor terminal
or
Relay connector
Normal
87.2"
104.1"
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20:~30:)
Vane motor
Measure the resistance of each heater element by using a tester.
Heater
(Only P·KAH type)
Normal Abnormal
15k" Open or short
Normal
Abnormal
P1.6, P2
123.3k"
0.467kW 240V
P2.5, P3, P4
82.3k"
0.7kW 240V
P5, P6
57.6k"
1.0kW 240V
Open or short
Protector
OFF:130i5:
ON :80i20:
OCT03-E-2.qxp 04.3.26 1:48 PM Page 43