Specifications

115
12-4. SELF-DIAGNOSIS ACTION TABLE
Error Code
Meaning of error code and detection method
Case Judgment and action
P1
Abnormality of room temperature ther-
mistor (TH1)
1 The unit is in three-minute resume pre-
vention mode if short/open of thermistor
is detected. Abnormal if the unit dose
not reset normally after three minutes.
(The unit returns to normal operation, if
it has normally reset.)
2 Constantly detected during Cooling, dry-
ing, and heating operation.
Short: 90: or more
Open: -40: or less
1 Defective thermistor character-
istics
2 Contact failure of connector
(CN20) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective indoor controller
board
13 Check resistance value of thermistor.
0: ······15.0k"
10: ····9.6k"
20: ····6.3k"
If you put force on (draw or bend) the lead wire
with measuring resistance value of thermistor
breaking of wire or contact failure can be
detected.
2 Check contact failure of connector (CN20)
on the indoor controller board.
Refer to page 128 to 130.
Put the power on again and check restart
after inserting connector again.
4 Check room temperature display on remote
controller.
Replace indoor controller board if there
is abnormal difference with actual room
temperature.
There is no abnormality if none of above
comes within the unit.
Put the power off, and on again to operate.
P2
Abnormality of pipe temperature ther-
mistor/Liquid (TH2)
1 The unit is in three-minute resume pre-
vention mode if short/open of thermistor
is detected. Abnormal if the unit does
not reset normally after three minutes.
(The unit returns to normal operation, if
it has normally reset.)
2 Constantly detected during Cooling, dry-
ing, and heating (except defrosting)
operation.
Short: 90: or more
Open: -40: or less
1 Defective thermistor
characteristics
2 Contact failure of connector
(CN21) on the indoor controller
board.(Insert failure)
3 Breaking of wire or contact
failure of thermistor wiring
4 Defective refrigerant circuit
is causing thermistor
temperature of 90: or more
or -40: or less.
5 Defective indoor controller
board.
13 Check resistance value of thermistor.
For characteristics, refer to (P1) above.
2 Check contact failure of connector (CN21)
on the indoor controller board.
Refer to page 128 to 130.
Put the power on and check restart after
inserting connector again.
4 Check pipe <liquid> temperature with remote
controller in trial run mode. If pipe <liquid>
temperature is exclusively low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defective.
5 Check pipe <liquid> temperature with remote
controller in trial run mode. If there is exclu-
sive difference with actual pipe <liquid> tem-
perature, replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Put the power off, and on again to operate.
P4
Abnormality of drain sensor (DS)
1 Suspensive abnormality, if short/open of
thermistor is detected for 30 seconds
continuously.
Put off compressor and indoor fan.
2 Short/open is detected for 30 seconds
continuously during suspensive abnor-
mality.
(The unit returns to normal operation, if
it has normally reset.)
3 Detect the following condition.
• During cooling and drying operation.
• In case that pipe <liquid> temperature-
room temperature <-10deg
(Except defrosting)
• When pipe <liquid> temperature or
room temperature is short/open tem-
perature.
• During drain pomp operation.
Short: 90: or more
Open: -20: or less
1 Defective thermistor character-
istics
2 Contact failure of connector
(CN31) on the indoor controller
board. (Insert failure)
3 Breaking of wire or contact
failure of drain sensor wiring
4 Defective indoor controller
board.
13 Check resistance value of thermistor.
0: ······6.0k"
10: ····3.9k"
20: ····2.6k"
30: ····1.8k"
40: ····1.3k"
2 Check contact failure of connector (CN31)
on the indoor controller board.
Refer to page 128 to 130.
Put the power on again and check restart
after inserting connector again.
4 Replace indoor controller board if drain
pomp operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited,
and abnormality reappears.
There is no abnormality if none of above
comes within the unit. Put the power off, and
on again to operate.
P5
Malfunction of drain pump (DP)
1 Suspensive abnormality, if thermistor of
drain sensor is let heat itself and tem-
perature rises slightly. Put off compres-
sor and indoor fan.
2 Drain pomp is abnormal if the condition
above is detected during suspensive
abnormality.
3 Constantly detected during drain pomp
operation.
1 Malfunction of drain pomp
2 Defective drain
Clogged drain pomp
Clogged drain pipe
3 Attached drop of water at the
drain sensor
• Drops of drain trickles from
lead wire.
• Clogged filter is causing
wave of drain.
4 Defective indoor controller
board.
1 Check if drain-up machine works.
2 Check drain function.
3 Check the setting of lead wire of drain sen-
sor and check clogs of the filter.
4 Replace indoor control p.c. board if drain
pomp operates with the line of drain sensor
connector CN31-1 and 2 is short-circuited
and abnormality reappears.
Refer to page 128 to 130.
There is no abnormality if none of above
comes within the unit. Put the power off, and
on again to operate.
30: ····1.8k"
40: ····1.3k"