Service manual
83
12
OPTIONAL PARTS
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as con-
nection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.
Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoor
units are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m, an additional charge of refrigerant in needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole).
1. REFRIGERANT PIPES
Service Ref. : PCH-2GKA-E / PCH-2.5GKA-E / PCH-3GKA-E
Service Ref. : PCH-4GKSA-E / PCH-5GKSA-E / PCH-6GKSA-E
2. TIMER
Part No.
PAC-SC32PTA
3. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using this controller, a program timer adapter (PAC-
825AD) is also needed.
Part No. PAC-805RC
4. PROGRAM TIMER ADAPTER
This part is needed when a centralized remote controller (PAC-805RC) is used.
Part No. PAC-825AD
5. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts.
Part No. PAC-SA89TA-E
6. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check).
Part No. PAC-SA88HA-E
Optional parts connection is described in the service technical guide No.OCT01.
Model name Program timer (when set back function)
Part No.
Pipe length
Pipe size O.D.
Connection method
PAC-05FFS-E
5m
PAC-07FFS-E
7m
PAC-10FFS-E
10m
PAC-15FFS-E
15m
Liquid : {9.52 Gas : {15.88
Indoor unit : Flared Outdoor unit : Flared
Part No.
Pipe length
Pipe size O.D.
Connection method
PAC-SC51PI-E
5m
PAC-SC52PI-E
7m
PAC-SC53PI-E
10m
PAC-SC54PI-E
15m
Liquid : {9.52 Gas : {19.05
Indoor unit : Flared Outdoor unit : Flared