Service manual
43
<HEAT operation time chart>
ON
Thermostat
Indoor fan
Auto vane
Drain pump
(OPTINAL)
Compressor
ON
ON
LOW or HIGH
LOW
or HIGH
ON
OFF
OFF
OFF
OFF
OFF
Power ON lamp
ON
OFF
STAND BY lamp
ON
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
close
close
Horizontal
1 Changeable by indoor
Jamper resistance
J1-7 and J1-8
w
w
w
From POWER ON until
warm begins to blow
Depends on remote
controller setting
Depends on remote
controller setting
Extra LOW 1Extra LOW 1 LOW
Minimum 3 minutes 2
Horizontal
w2 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-3 HEAT operation
FILTER
CHECK MODE
TEST RUN
4
<How to operate>
1 Press POWER ON/OFF button.
2 Press the a button to display “ g ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Heating 17°C to 28°C
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost
operation.
[STANDBY]
The [STANDBY] symbol is displayed from the heating operation
starts until the heated air begins to blow.