Service manual
41
<DRY operation time chart>
ON
Thermostat
Indoor fan
Auto vane
Drain pump
(OPTIONAL)
Compressor
ON
ON
Low speed
LOW speed
ON
OFF
OFF
3 minutes
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
Initially horizontal
close
close
Minimum 3 minutes w1
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until this period has ended.
2-2 DRY operation
(1) Compressor control
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when the room temperature is higher than the set temperature.
The compressor stops when the room temperature is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions.
FILTER
CHECK MODE
TEST RUN
4
<How to operate>
1 Press POWER ON/OFF button.
2 Press the a button to display “ e ”.
3 Press the i TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Dry 19°C to 30°C.