Submittal

Job Name: Location:
Drawing Reference: Schedule No.
System No.: Date:
Model: PAR-FL32MA Controller
and PAR-FA32MA Receiver
PAR-FL32MA WIRELESS MA REMOTE CONTROLLER
SPECIFICATIONS
• UsedinconjunctionwithPAR-FA32MAMARemote
ControllerReceiver.
• Maximumsignalreceivingdistanceisapproximately22'(7m).
• Maximumsignalreceivingangleisapproximately45tothe
leftandrightofcenter.
• Installaminimumof3'(1m)awayfromatelevisionorradio.
• Controlsgroupoperationforupto16indoorunitsina
singlegroup.
• SupportsbothFahrenheitandCelsius.
• UserFunctionsallowsusertoset:
-On/Off
-SetTemperature
-OperationMode(Heat,Cool,Dry,Fan,Auto[R2-Series
only])
-FanSpeedsetting
-Airowdirection(dependingonindoorunit)
• Rangeofsettemperaturedependsontheindoorunit:
Cool/Dry:67°Fto87°F/19°Cto30°C
Heat:63°Fto83°F/17°Cto28°C
Auto:67°Fto83°F/19°Cto28°C
• On/Offtimer:OneOn/Offsettingforoneday.
• FunctionLockout:Individuallyprohibitsallfunctionsof
eachremotecontroller.
• Grouping:Canonlybeusedinsamegroupwith
PAC-YT51CRASimpleMARemoteControllers,
PAR-21MAADeluxeMARemoteControllers,andother
wirelessreceiverswithuptotworemotecontrollersper
group.Wirelessremotecontrollercannotgroupindoorunits
servedbyseparateoutdoorunits.
• Dimensions:2-1/4"Wx6-1/4"Hx3/4"D(58x159x19mm).
ON/OFF
COOLHEAT
PAR-FL32MA PA R-FA32MA
(Signal receiving unit)
Signal
receiving
unit
Signal
receiving
unit
Non-polarized
2-wire
Non-
polarized
2-wire
Non-
polarized
2-wire
Wireless
remote
controller
Wireless
remote
controller
Signal
receiving
unit
Wireless
remote
controller
PAR-FA32MA WIRELESS MA REMOTE CONTROLLER
RECEIVER SPECIFICATIONS
• On/Offlamptoindicateunitoperationanderrorstatus.
• Enableheatandcooloperation(atpre-setparameters)from
thereceiverforwhentheremoteisnotoperational.
• Wiring:Connectsusingtwo-wire,stranded,non-polar
controlwiretoTB-15connectionterminalontheindoor
unit.Requirescrossoverwiringforgroupingacrossindoor
units.
• Dimensions:2-3/4"Wx4-3/4"Hx7/8"D(70x120x23mm).
OVERVIEW OF CITY MULTI
®
CONTROLS
NETWORK
(CMCN)
• ConsistsofTG-2000integratedsystemsoftware,AG-150/
GB-50ADA/GB-24/TC-24centralizedcontrollers,web
browsers,timers,remotecontrollers,andBMSinterfaces.
• TG-2000integratedsystemsoftwaresupportsupto40
AG-150/GB-50ADAcentralizedcontrollers(licensedfor
PCsoftwarefeatures)foramaximumof2,000indoor
unitsfromasinglePC.
• AG-150centralizedcontrolleroperatesupto50indoor
unitswithoptionalcontrolviaaeld-suppliedPCwith
licensedsoftware.
• GB-50ADAcentralizedcontrolleroperatesupto50
indoorunitsviaaeld-suppliedPCwithlicensed
software.
• GB-24centralcontrolleroperatesupto24indoorunits
viaaeld-suppliedPCwithlicensedsoftware.
• TC-24standalonecentralizedcontrolleroperatesupto24
indoorunitsviaanintegraltouchscreeninterface.
• RemotecontrollersconsistofDeluxeMA,SimpleMA
WirelessMA,andME.
• I/OcontrollersconsistofDIDO(PAC-YG66DCA)and
AI(PAC-YG63MCA)forthird-partyequipmentcontrol.
• LonWorks
®
andBACnet
®
interfacesalsoavailable.
• InterlockingofLOSSNAY
®
ERVunitsforcontrolvia
theAG-150/GB-50ADA/GB-24/TC-24centralized
controllers.