Unit Function Setting by the Remote Controller (for Mr. SLIM)
(2) Itemised functions of the indoor unit
(select unit numbers 01 to 03 or AL [ Wired remote controller ] / 07 [ Wireless remote controller ])
Function Settings
Mode No. Setting No. Check Remarks
Filter sign
100Hr
07
1
2500Hr 2
"Clean the filter" indicator is not displayed 3
Air flo
(Fan speed)
*2
Silent Standard
PLA-RP·AA type 08
1
Standard High
ceiling
1
2
High ceiling High ceiling
2
3
No.
of
air outlets
(not for SLZ)
4 directions
09
1
3 directions 2
2
directions 3
Installed options
(high performance filter) *
Not supported
1
0
1
Supported 2
Vane
setting
No vanes (Vane No.3 setting : PLA only)
11
1
Vane
No. 1 setting 2
Vane
No. 2 setting 3
Swing
Not available
Swing
PLA-RP·BA type 23
1
Available
Wave air flo 2
Set temperature
in heating
mode 4deg-up *1
ON
24
1
OFF 2
Fan speed
when the heat-
ing thermostat
is OFF *1
Extra low
25
1
Stop 2
Set fan
speed 3
Fan speed
when the cool-
ing thermostat
is OFF
Set fan speed
27
1
Stop 2
Detection of abnormality (P8)
of the pipe temperature
Detect
28
1
Neglect 2
*1 SLZ/SEZ-KC/SEZ-KA type : when SW3-5 (indoor controller board) is ON, the setting of SW3 takes precedence.
SW3
Function
setting
Dip
switch Function
Action by
switch operation
OFF ON
SW3-1
Power
failure
automatic recovery
OFF ON
SW3-2
Set
temperature
in
heating mode (4 deg up)
Available Not
available
SW3-3
Fan speed
when the
heating the thermostat is OFF
Extra low Stop
SW3-4 — — —
SW3-5* SW3
function Not
available Available
· Function
setting becomes effective, when the Dip switch SW3-5 is ON.
* Switch off SW3-5 when the function setting is done by wired remote controller.
· SEZ-KD·VA(L) model is excluded.
*2 SEZ-KD · VA(L) MODE No. 08,10
Function Settings
Mode No. Setting No. Check Remarks
External static pressure
15Pa
08
1
35Pa 2
50Pa 3
The same as setting of mode No. 08
10
1
5Pa (set
made No. 08 to 1) 2
Note
If a function of an indoor unit is changed by function selection after installation is complete, make sure that a “ ” mark, etc., is given in the
“Check” column of Table to indicate the change