Specifications

PUHY-P YHA(-BS)
OUTDOOR UNIT
Y Series
Specifications
Power source
Cooling capacity
(Nominal)
Temp.
range of
cooling
Heating capacity
(Nominal)
Temp.
range
of heating
Indoor unit
connectable
Sound pressure level
(measured in anechoic room)
Power pressure level
(measured in anechoic room)
Diameter of
refrigerant pipe
External finish
External dimension H x W x D
Net weight
Heat exchanger
Compressor
FAN
Protection
devices
Refrigerant
Optional parts
45.0
153,500
13.23
22.3-21.2-20.4
3.40
50.0
170,600
13.47
22.7-21.6-20.8
3.71
P15~P250 / 1~34
61
81
ø12.7 (ø1/2) Brazed
ø28.58 (ø1-1/8) Brazed
1,650 x 1,220 x 760
65 x 48-1/16 x 29-15/16
245 (541)
10.5
225
3,750
7,945
Propeller fan x 1
0.92 x 1
Thermal switch
R410A x 11.5kg (26 lbs)
joint : CMY-Y102SS / LS-G2, CMY-Y202S-G2
Header : CMY-Y104 / 108 / 1010-G
50.0
170,600
16.66
28.1-26.7-25.7
3.00
52.0
177,400
15.85
26.7-25.4-24.5
3.28
P15~P250 / 1~39
62
82
ø15.88 (ø5/8) Brazed
ø28.58 (ø1-1/8) Brazed
1,650 x 1,220 x 760
65 x 48-1/16 x 29-15/16
245 (541)
12.0
225
3,750
7,945
Propeller fan x 1
0.92 x 1
Thermal switch
R410A x 11.5kg (26 lbs)
Power input
Current input
COP (kW/kW)
Indoor
Outdoor
Power input
Current input
COP (kW/kW)
Indoor temp.
Outdoor temp.
Total capacity
Model/Quantity
Liquid
Gas
Type
Starting method
Motor output
Air flow rate
Type x Quantity
Motor output
High pressure protection
Inverter circuit
Fan motor
Type
x
Original charge
kW
BTU/h
kW
A
W.B.
D.B.
kW
BTU/h
kW
A
D.B.
W.B.
dB<A>
dB<A>
mm(in.)
mm(in.)
mm
in.
kg(lbs)
kW
m
3
/min
L/s
cfm
kW
*1
*1
*2
*2
PUHY-P400YHA(-BS) PUHY-P450YHA(-BS)
15~24°C (59~75°F)
- 5~46°C (23~115°F)
15~27°C (59~81°F)
-20~15.5°C (-4~60°F)
50~130% of outdoor unit capacity
Pre-coated galvanized steel sheets (+ powder coating for-BS type) <MUNSELL 3.0Y 7.8/11 or similar>
Salt-resistant cross fin & copper tube
Inverter scroll hermetic compressor
Inverter
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-current protection
3-phase 4-wire 380-400-415V 50/60Hz
PUHY-P350YHA(-BS)
40.0
136,500
11.20
18.9-17.9-17.3
3.57
45.0
153,500
12.09
20.4-19.3-18.6
3.72
P15~P250 / 1~30
60
80
ø12.7 (ø1/2) Brazed
ø28.58 (ø1-1/8) Brazed
1,650 x 1,220 x 760
65 x 48-1/16 x 29-15/16
245 (541)
10.3
225
3,750
7,945
Propeller fan x 1
0.92 x 1
Thermal switch
R410A x 11.5kg (26 lbs)
PUHY-P YHA(-BS)
OUTDOOR UNIT
Y Series
Specifications
Power source
Cooling capacity
(Nominal)
Temp.
range of
cooling
Heating capacity
(Nominal)
Temp.
range
of heating
Indoor unit
connectable
Sound pressure level
(measured in anechoic room)
Power pressure level
(measured in anechoic room)
Diameter of
refrigerant pipe
External finish
External dimension H x W x D
Net weight
Heat exchanger
Compressor
FAN
Protection
devices
Refrigerant
Optional parts
Power input
Current input
COP (kW/kW)
Indoor
Outdoor
Power input
Current input
COP (kW/kW)
Indoor temp.
Outdoor temp.
Total capacity
Model/Quantity
Liquid
Gas
Type
Starting method
Motor output
Air flow rate
Type x Quantity
Motor output
High pressure protection
Inverter circuit
Fan motor
Type
x
Original charge
kW
BTU/h
kW
A
W.B.
D.B.
kW
BTU/h
kW
A
D.B.
W.B.
dB<A>
dB<A>
mm(in.)
mm(in.)
mm
in.
kg(lbs)
kW
m
3
/min
L/s
cfm
kW
*1
*1
*2
*2
PUHY-P200YHA(-BS) PUHY-P250YHA(-BS) PUHY-P300YHA(-BS)
22.4
76,400
5.72
9.6-9.1-8.8
3.91
25.0
85,300
6.03
10.1-9.6-9.3
4.14
P15~P250 / 1~17
56
76
ø9.52 (ø3/8) Brazed
ø19.05 (ø3/4) Brazed
1,650 x 920 x 760
65 x 36-1/4 x 29-15/16
185 (408)
5.4
185
3,083
6,532
Propeller fan x 1
0.92 x 1
Thermal switch
R410A x 6.5kg (15 lbs)
joint : CMY-Y102SS-G2
Header : CMY-Y104 / 108 / 1010-G
28.0
95,500
7.73
13.0-12.3-11.9
3.62
31.5
107,500
7.83
13.2-12.5-12.1
4.02
P15~P250 / 1~21
57
77
ø9.52 (ø3/8) Brazed
(ø12.7 (ø1/2) Brazed , total length >=90m)
ø22.2 (ø7/8) Brazed
1,650 x 920 x 760
65 x 36-1/4 x 29-15/16
200 (441)
6.7
185
3,083
6,532
Propeller fan x 1
0.92 x 1
Thermal switch
R410A x 9.0kg (20 lbs)
33.5
114,300
9.07
15.3-14.5-14.0
3.69
37.5
128,000
9.39
15.8-15.0-14.5
3.99
P15~P250 / 1~26
59
79
ø9.52 (ø3/8) Brazed
(ø12.7 (ø1/2) Brazed , total length>=40m)
ø22.2 (ø7/8) Brazed
1,650 x 920 x 760
65 x 36-1/4 x 29-15/16
215 (474)
8.2
185
3,083
6,532
Propeller fan x 1
0.92 x 1
Thermal switch
R410A x 9.0kg (20 lbs)
3-phase 4-wire 380-400-415V 50/60Hz
15~24°C(59~75°F)
- 5~46°C(23~115°F)
15~27°C(59~81°F)
-20~15.5°C(-4~60°F)
50~130% of outdoor unit capacity
Salt-resistant cross fin & copper tube
Inverter scroll hermetic compressor
Inverter
Pre-coated galvanized steel sheets (+ powder coating for-BS type) <MUNSELL 3.0Y 7.8/11 or similar>
High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Over-current protection
joint : CMY-Y102SS / LS-G2
Header : CMY-Y104 / 108 / 1010-G
Notes:
*1,*2 Nominal conditions
*Nominal condition *1,*2 are subject to JIS B8615-2.
*Due to continuing improvement, above specification may be subject to change without notice.
Indoor Outdoor Pipe length Level difference
Cooling
27ºC DB/19ºC WB
(81ºF DB/66ºF WB)
35ºC DB(95ºF DB) 7.5m (24-9/16ft.) 0m (0ft.)
Heating 20ºC DB(68ºF DB) 7ºC DB/6ºC WB(45ºF DB/43ºF WB) 7.5m (24-9/16ft.) 0m (0ft.)
Notes:
*1,*2 Nominal conditions
*Nominal condition *1,*2 are subject to JIS B8615-2.
*Due to continuing improvement, above specification may be subject to change without notice.
Indoor Outdoor Pipe length Level difference
Cooling
27ºC DB/19ºC WB
(81ºF DB/66ºF WB)
35ºC DB(95ºF DB) 7.5m (24-9/16ft.) 0m (0ft.)
Heating 20ºC DB(68ºF DB) 7ºC DB/6ºC WB(45ºF DB/43ºF WB) 7.5m (24-9/16ft.) 0m (0ft.)
Page 79
Outdoor unit
Page 80
Outdoor Unit