Submittal

System Reference: Date:
AVAILABLE MODELS
MAC-640BH-U
MAC-642BH-U1
PAC-645BH-E
PAC-646BH-E
PAC-SJ20BH-E
GENERAL FEATURES
Prevents ice from building up on the outdoor unit base
when operating in heating mode for an extended period
of time in a very low temperature, high humidity
condition
Controlled by outdoor unit
Works during defrost operation and energizes when
outdoor temperature drops below 36ºF
MAC-640BH-U connects to CN722 on control board of
MUZ-FH06,09,12NA, MUZ-GL09,12,15NA, MUZ-
HM09,12,15,18NA, MUZ-WR09,12,18NA, SUZ-
KA09,12,15NA2
PAC-645BE-E connects to CN-714 on
MXZ-3C24/3C30/4C36/5C42NA
MAC-642BH-U1 connects to CN601 on control board of
MUZ-FH15,18NA, MUZ-GL18,24NA, MUZ-HM24NA,
MUZ-WR24NA, SUZ-KA18,24,30,36NA2
PAC-646BH-E connect to CN714 on MXZ-2C20NA2
PAC-SJ20BH-E connects SS on Control board of
MXZ-8C48NA, 8C60NA, PUZ-A36,42NKA7, PUZ-
HA42NKA, PUMY-P36,48,60NKMU2
INSTALLATION NOTES
For MUZ-A models, the power board needs to be
replaced with board included with pan heater
Use of drain pan heaters is recommended when ambient
temperatures are expected to be below freezing for
periods longer than 72 hours straight; or when
continuous sub-zero outdoor ambient conditions are
expected to last longer than 24 hours
Outdoor unit must not be installed directly on the ground,
but on a raised platform, such as on mini-split stands, to
suppress freezing
Recommended installation of a Ground Fault Interrupt
(GFI) circuit breaker, depending on installation area to
prevent electric shock
See corresponding installation instructions, and outdoor
unit technical service manual for further details on
installation
DRAIN PAN HEATERS
LOW AMBIENT BASE P
AN HEATERS
Specifications are subject to change without notice. © 2019 Mitsubishi Electric Trane HVAC US LLC