Specifications

-82-
(11) Liquid Refrigerant Correction Control
The liquid refrigerant correction control adjusts the liquid refrigerant amounts between both accumulators in the
unlikely event that the liquid refrigerant amount in both the constant and variable capacity unit accumulators should
be insufficient, or if excessive amount of liquid refrigerant is returned to either accumulator.
During this operation, Service LED No. 4 on the variable capacity unit will light up.
Direction of Accumula-
tor Liquid Transfer
Variable Capacity Unit
Constant Capacity Unit
Indoor Unit
Variable Capacity Unit
Constant Capacity Unit
Variable Capacity Unit
Constant Capacity Unit
Variable Capacity Unit
Constant Capacity Unit
Variable Capacity Unit
Constant Capacity Unit
Constant Capacity Unit
Variable Capacity Unit
Constant Capacity Unit
Variable Capacity Unit
Start Conditions
In heating mode
Run and stop indoor units
are mixed.
Pd 13k (1.27 MPa), or
during an accumulator
overflow preliminary error.
Td < 110˚C
In heating mode
While the constant capacity
unit is stopped.
During an accumulator
overflow preliminary error
in the variable capacity unit
(AL1 = 2)
TdSH < 40 deg *1
In heating mode
During constant capacity
unit operation
When AL1 = 2 is detected in
the variable capacity unit.
TdSH < 40 deg *1
In cooling mode
While the constant capacity
unit is stopped.
During an accumulator
overflow preliminary error
in the variable capacity unit
(AL1 = 2)
Constant capacity unit
AL2 = 0 or 1
Variable capacity unit
TH6 < 25˚C
In heating mode
Constant capacity unit
switches from operation to
stopping.
Constant capacity unit AL2 = 0
In heating mode
During an accumulator
overflow error delay in the
constant capacity unit
(AL2 = 2)
Variable capacity unit
AL1 = 0 or 1
During cooling or heating
During an accumulator
overflow preliminary error
in the constant capacity
unit (AL2 = 2)
Variable capacity unit
AL1 = 0 or 1
Actuator Action
Com-
pressor
OFF
OFF
OFF
OFF
OFF
Constant Capacity Unit
Variable
capacity
unit
Opera-
tion
fre-
quency
level
up
Opera-
tion
fre-
quency
level
down
21S4a,
b
ON
Indoor
Unit
Opera-
tion:
nor-
mal
control
Stop:
LEV = 60
All
indoor
unit
LEV = 60
All
indoor
unit
LEV = 60
Stopping
Conditions
While all
indoor units
are operat-
ing
Td 115˚C
AL1 = 0 or 1
Continuing
for 20
minutes
AL1 = 0 or 1
AL2 = 2
Continuing
for 10
minutes
AL1 = 0 or 1
Continuing
for 15
minutes
AL1 = 0 or 1
Continuing
for 3 ~ 6
minutes
AL2 = 0 or 1
AL1 = 2
Continuing
for 10
minutes
AL1 = 2
Continuing
for 4
minutes
LED Monitor
No.4
Verify
surplus
refrigerant
LD1 lights
up
Liquid
refrigerant
control
LD3 lights
up
Liquid
refrigerant
control
LD5 lights
up
Liquid
refrigerant
control
LD7 lights
up
Liquid
refrigerant
control
LD8 lights
up
Liquid
refrigerant
control
LD4 lights
up
Liquid
refrigerant
control
LD6 lights
up
LEV2
2000
2000
2000
2000
2000
SV5b
ON
(open)
ON
(open)
ON
(open)
ON
(open)
ON
(open)
Other
Fa n
ON
LEV1 =
480
SV4 ON
21S4
OFF
* 1 TdSH (Discharge temperature superheating) = Discharge temperature (TH11 or TH12) - Tc (High pressure satur
ation
temperature)
2
4
6
7
3
5