(5) Oil return control (Electronic expansion valve (SLEV))
The amount of opening of the oil-return LEV (SLEV) is determined as follows: in cooling, by the operating
of the No. 1 compressor and the ambient temperature; in heating, by the operating capacity of the
It is opened (64) when both compressors are stopped and started for 10 minutes. (Upper limit of LEV opening
= 388 pulse.)
SLEV = 0 when the No. 1 compressor is stopped.
capacity
(6) Sub-cool coil control (Electronic expansion valve (LEV1))
The sub-cool coil control provides control every 30 seconds to keep the super heat volume from the temperature
the inlet/outlet of the sub-cool coil (TH8, TH9) within a stable range (2 to 4 degrees).
It controls by correcting the amount of opening according to the temperature of the inlet/outlet of the sub-cool
(TH5, TH7), the high pressure (Pd) and discharge temperature.
It is closed (0) in heating or when the compressor is stopped.
It has a fixed opening (480) in defrosting.
During normal control, the operating range is 46 to 480.
(7) Defrosting control
1) Start of defrosting
After there has been heating operation for 50 minutes or after 90 minutes has passed and a piping temperature
(TH5) of 0˚C or less is detected for a preset time, defrosting begins.
When 10 minutes has passed since the compressor began operation or if 10 minutes has passed since recovery
from defrosting, setting the forced defrosting switch (Dip SW2-7) to starts forced defrosting.
2) End of defrosting
Defrosting ends when 15 minutes has passed since the start of defrosting or when the piping temperature (TH5)
becomes 7˚C or more. (Note that if defrost-prohibited time has been set to 90 minutes, the defrost-prohibit time will
be 50 minutes following a 15 minute timed recovery.)
Ending the defrosting is prohibited for 2 minutes after the start of defrosting. (Note that the defrosting operation will
be ended if the piping temperature exceeds 20˚C within 2 minutes of the start of defrosting.
3) Defrost-prohibit
Defrosting is not performed for 10 minutes after the start of compressor operation and during oil recovery mode.
4) Abnormalities during defrosting
If an error is detected during defrosting, the defrosting is stopped and the defrost-prohibit time is set to 20 minutes
by the compressor cumulative operating time
.
No. 1 compressor.