Specifications

-67-
Item
At compressor is started
Compressor stopped during cool-
ing or heating mode
After operation has been stopped
During defrosting ((*1) in Fig below)
During oil recovery operation
When low pressure saturation
temperature (TH2) has dropped
during lower limit frequency opera-
tion(15 minutes after start)
When the high pressure (Pd) is
risen up during lower limit fre-
quency operation (3 minutes after
starting)
When the discharge temperature
(Td) is risen up
TH2 15˚C
Pd
2.26 MPa and
after
30 seconds
Pd
1.96 MPa
Td
115˚C
* Example of operation of SV1
Compressor
Bypass
solenoid
valve (SV1)
(4-minute)
(2-minute) (4-minute) (3-minute)
Start
Thermo.
OFF
Thermo.
ON
Defrost
Stop
2) Bypass solenoid valves (SV1, SV4) [Both SV1 and SV4 are on (open)]
ON OFF
SV1
ON for 4 minutes
ON
ON for 3 minutes
ON
ON during oil recovery operation af-
ter continuous low-frequency com-
pressor operation.
ON
TH2 < 30˚C
Pd
2.26 MPa
ON when the high pres-
sure (Pd) exceeds the
control pressure limit.
Td > 130˚C
and
Pd >
1.96 MPa
or
TH2 < 10˚C
OFF
SV4
Normally ON
3) Capacity control solenoid valve (SV22, SV32) *Model 500 only.
Operation of solenoid valve
SV22 and SV32 stand for SV2 and SV3 of the No. 2
compressor.
Solenoid valve
SV22
SV32
COMP
SV22 SV32
Coil Valve Coil Valve
OFF Open OFF Closed
ON Closed ON Open
Status
Full-load
(Operating at 100 %
capacity)
Un-load
(Capacity control
operation)
Pd
2.70 MPa
Pd
2.35
MPa
and
after 30 seconds
.