Specifications

-112-
Detects the outdoor air temperature.
Performs fan control, liquid level
heater control, opening settings of
LEV for oil return and other functions.
Thermistor
R0 = 15 k
B
1/80 = 3460
Rt =
15exp{3460( - )}
0°C: 15 k
10°C: 9.7 k
20°C: 6.4 k
25°C: 5.3 k
30°C: 4.3 k
40°C: 3.1 k
Resistance checkTH6
(Outdoor
temperature)
TH7
TH8
TH9a
(SC control)
(P400,
P500 only)
Name
Code
(Function)
Inspection methodApplication
Product code
Specification
1
273+t
1
273
1
273+t
1
273
1
273+t
1
273+120
1
273+t
1
323
Resistance checkTH3
TH4
(Liquid level
detection)
TH5
(Liquid pipe
temperature)
Detects liquid level of refrigerant inside
accumulator using the differences
among TH2, TH3, TH4.
1 Frequency control.
2 Controls defrosting during heating.
Resistance check
Conductivity test
using tester
TH10c
(P400,
P500 only)
1) Detects the compressor shell
temperature.
2) Provides compressor shell over-
heating protection.
Inverter cooling fan control using THHS
temperature.
1 Capacity control of high/low
pressure bypass when starting and
stopping.
2
Discharge pressure rise suppression.
Switching of capacity control valve inside
No. 2 compressor (Switching between
full load operation and unload operation)
(All but 400).
Capacity control and controlling the rise
of high-pressure (Back-up of frequency
control).
R120 = 7.465 k
B25/120 = 4057
Rt =
7.465exp
{4057( - )}
20°C: 250 k 70°C: 34 k
30°C: 160 k 80°C: 24 k
40°C: 104 k 90°C: 17.5 k
50°C: 70 k 100°C: 13.0 k
60°C: 48 k 110°C: 9.8 k
R50 = 17 k
B
25/120 = 4170
Rt =
17exp {4170 ( - )}
0°C: 181 k
10°C: 105 k
20°C: 64 k
25°C: 50 k
30°C: 40 k
40°C: 26 k
AC 220 to 240 V
Open : conducting
Close: not conducting
AC 220 to 240 V
Close: conducting
Open : not conducting
AC 220 to 240 V
Open : conducting
Close: not conducting
THHS inverter
heat sink tem-
perature
SV1
discharge-
suction
bypass
SV22
capacity
control (full
load)
SV32
capacity
control
(unload)
SV4
discharge-
suction
bypas
s
TH9b
Controls LEV using temperature
differences among TH5, TH7, TH8
and TH9a.
1) Detects the CS circuit fluid tempera-
ture.
2) Calculates the refrigerant circulation
configuration.
R
0 = 15 k
B
1/80 = 3460
Rt =
15exp{3460( - )}
0°C: 15 k
10°C: 9.7 k
20°C: 6.4 k
25°C: 5.3 k
30°C: 4.3 k
40°C: 3.1 k
Solenoid
valve
Outdoor unit (Variable capacity unit)
1
2
Performs constant capacity unit LEV2
control by comparing the temperature
difference with low pressure saturation
temperature.
TH10a
TH10b
Heat
exchanger
Gas tempera-
ture