Specifications

-111-
1 Adjustment of super heat of heat
exchanger outlet port of indoor unit
during cooling.
2 Adjustment of sub-cool of heat ex-
changer outlet port of indoor unit
during heating.
Indoor unit control (Thermostat).
1 Indoor unit control (Freeze preven-
tion, hot adjust, etc.).
2 LEV control during heating (sub-cool
detection).
LEV control during cooling (super-heat
detection).
Uses the operating pressure to adjust
the operating frequency and adjust the
amount of circulating refrigerant.
When there is a load that cannot be
adjusted by MC1, this function ensures
the stable flow of refrigerant.
[3] List of Major Component Functions
Name
Code
(Function)
Electronic
expansion
valve
Thermistor
Compres-
sor
Outdoor unit (Variable capacity unit)
Inspection method
DC 12 V
Amount of opening of the
stepping motor drive valve
60 to 2000 pulse.
(Gear Type)
R
0 = 15 k
B
0/80 = 3460
Rt =
15exp{3460( - )}
0°C: 15 k
10°C: 9.7 k
20°C: 6.4 k
25°C: 5.3 k
30°C: 4.3 k
40°C: 3.1 k
Low-pressure shell scroll
type. Winding resitance
0.481 (20°C).
Low-pressure shell scroll type.
Winding resistance: each phase.
1.996 (20°C): P400 YMF-C
1.197 (20°C): P500 YMF-C
1
273+t
1
273
1
273+t
1
393
Application
Product code
Specification
Indoor unit
LEV
TH21
(Inlet air
temperature)
TH22
(Piping
temperature)
TH23
(Gas piping
temperature)
MC1
MC2
White
Red
Yellow Brown Blue
Orange
M
Perform a continuity
check using a tester.
Conductivity among
white, red and orange.
Conductivity among yel-
low, brown and blue.
Resistance value
check
Con-
nector
1
273+t
1
273
63HS
Pressure
0.3 V/MPa
Gnd (black)
Vout (white)
Vc (DC 5 V) (Red)
Con-
nector
63LS
R120 = 7.465 k
B
25/120 = 4057
Rt =
7.465exp{4057( - )}
R0 = 33 k
B0/100 = 3965
R
t =
33exp{3965( - )}
20°C: 92 k
10°C: 55 k
0°C: 33 k
10°C: 55 k
20°C: 13 k
30°C: 8.2 k
1 Detects high-pressure pressure.
2 Performs frequency control and high-
pressure protection.
1) Detects low-pressure.
2) Calculates the refrigerant circula-
tion configuration.
3) Protects the low pressure
Detects high-pressure.
Performs high-pressure protection.
Detects high-pressure pressure.
Performs high-pressure protection.
0°C: 698 k 60°C: 48 k
10°C: 413 k 70°C: 34 k
20°C: 250 k 80°C: 24 k
30°C: 160 k 90°C: 17.5 k
40°C: 104 k 100°C: 13.0 k
50°C: 70 k 110°C: 9.8 k
Detects low pressure saturation tem-
perature.
Performs frequency control and liq-
uid level of accumulator.
High
pressure
sensor
Low
pressure
sensor
Pressure
switch
Thermistor
63HS
63LS
63H1
62H2
TH11,12
(Outlet)
TH2 (Low
pressure
saturation
temperature)
Conductivity check
Resistance check
Resistance check
0 to 0.98 MPa
Vout 0.5 to 3.5 V
Set to 2.94 MPa OFF.
Pressure
Vout 0.5 to 3.5 V
Connector
GND (Black)
Vout (White)
Vc (DC 5 V) (Red)
0 to 2.94 MPa
1
2
1
2
1
2