M-Series - MSZ/MUZ-GENA2 Heat Pump Systems (August 2014)
MSZ-GENA2-9
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-1. SPECIFICATIONS
Model name
MUZ-GE15NA2 MUZ-GE18NA-1
Capacity
Rated
(Minimum~Maximum)
Cooling 1 Btu/h
14,000
( 3,100 ~ 18,200 )
17,200
( 3,700 ~ 18,700 )
Heating 47 1 Btu/h
18,000
( 4,800 ~ 20,900 )
21,600
( 3,500 ~ 25,200 )
Capacity
Rated (Maximum)
Heating 17 2 Btu/h
11,300 (15,900)
13,400 (17,200)
Power con-
sumption
Rated
(Minimum~Maximum)
Cooling 1 W
1,080 (160 ~ 2,000) 1,640 (240 ~ 2,070)
Heating 47 1 W
1,600 (270 ~ 2,010) 1,900 (230 ~ 2,680)
Power consumption
Rated (Maximum)
Heating 17 2 W 1,150 (1,950) 1,450 (2,080)
EER
1
[SEER]
3 Cooling 13.6 [ 21.6] 10.5 [19.2]
HSPF IV 4 Heating
11.2
10.0
COP Heating
1 3.30 3.33
Power supply V , phase , Hz 208/230 , 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 12 14
Fan Motor (ECM) F.L.A 0.50 0.93
Compressor
Model SNB130FQBH
R.L.A 7.4 10.0
L.R.A 9.3 12.5
Refrigeration oil
Fl.Oz.
(Type)
15.2 (NEO22)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 49 54
Heating dB(A) 51 56
Defrost method Reverse cycle
Dimensions
W in. 31-1/2 33-1/16
D in. 11-1/4 13
H in. 21-5/8 33-7/16
Weight Ib. 80 119
External nish Munsell 3Y 7.8/1.1
Remote controller Wireless type
Control voltage
(by built-in transformer)
VDC 12 - 24
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 1/4 (0.0315)
Gas in. 1/2 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor
& outdoor units
Height difference ft. 40 50
Piping length ft. 65 100
Refrigerant charge (R410A) 2 lb. 9 oz. 3 lb. 7 oz.
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) — Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2: (Heating) — Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB Maximum frequency
MUZ-GE15NA2 MUZ-GE18NA-1