M-Series MZ-GE Engineering Manual

MSZ-GENA2-8
M-Series - MSZ/MUZ-GENA2 Heat Pump Systems (August 2014)
Due to continuing improvement, above specication may be subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
3-1. SPECIFICATIONS
Model name
MUZ-GE09NA2 MUZ-GE12NA2
Capacity
Rated (Minimum~Maximum)
Cooling 1 Btu/h
9,000
( 3,800 ~ 12,200 )
12,000
( 3,800 ~ 13,600 )
Heating 47 1 Btu/h
10,900
( 4,500 ~ 14,100 )
14,400
( 5,500 ~ 18,100 )
Capacity
Rated (Maximum)
Heating 17 2 Btu/h 6,600 (8,700)
8,800 (11,200)
Power consumption
Rated (Minimum~Maximum)
Cooling 1 W
660 (205~1,200) 960 (205~1,300)
Heating 47 1 W
760 (255~1,200) 1,170 (340~1,660)
Power consumption
Rated (Maximum)
Heating 17 2 W
700 (950) 900 (1,200)
EER
1
[SEER]
3 Cooling 13.6 [23.2] 12.5 [22.7]
HSPF IV
4 Heating
11.0 11.4
COP Heating
1 4.20 3.61
Power supply V , phase , Hz
208/230 , 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 12 12
Fan Motor (ECM) F.L.A 0.50
Compressor
Model KNB073FQDHC
KNB092FQAHC
R.L.A
6.6 6.6
L.R.A 8.2 8.2
Refrigeration oil
Fl.Oz.
(Type)
10.22 (NEO22)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 46 49
Heating dB(A) 50 51
Defrost method Reverse cycle
Dimensions
W in. 31-1/2
D in. 11-1/4
H in. 21-5/8
Weight Ib. 66 77
External nish Munsell 3Y 7.8/1.1
Remote controller Wireless type
Control voltage
(by built-in transformer)
VDC 12 - 24
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 1/4 (0.0315)
Gas in. 3/8 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor &
outdoor units
Height difference ft. 40
Piping length ft. 65
Refrigerant charge (R410A) 1 lb. 12 oz. 2 lb. 9 oz.
NOTE: Test conditions are based on ARI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB) Rated frequency
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB Rated frequency
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB Maximum frequency
MUZ-GE09NA2 MUZ-GE12NA2