M-Series MZ-GE Engineering Manual
Table Of Contents
- Contents
- 1. INDOOR UNITS
- 2. OUTDOOR UNITS
- 3. SYSTEM
- 3-1. SPECIFICATIONS
- 3-2. EXTERNAL DIMENSIONS
- 3-3. CENTER OF GRAVITY
- 3-4. ELECTRICAL WIRING DIAGRAMS
- 3-5. REFRIGERANT SYSTEM DIAGRAMS
- 3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
- 3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
- 3-8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH
- 3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
- 3-10. CHARGE CALCULATIONS
- 3-11. AIR FLOW DATA
- 3-12. SOUND PRESSURE LEVELS
- 3-13. STANDARD OPERATION RANGE
- 3-14. MAXIMUM HEATING CAPACITY IN LOW AMBIENT TEMPERATURE
- 3-15. ACCESSORIES
M-Series - MSZ/MUZ-GENA2 Heat Pump Systems (August 2014)
MSZ-GENA2-41
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-14. MAXIMUM HEATING CAPACITY IN LOW AMBIENT TEMPERATURE
HEATING CAPACITY
-13.0 -4.0 5.0 14.0 23.0 32.0 41.0 50.0 69.8
0%
20%
40%
60%
80%
100%
120%
-15 -5 5 15 25 35 45
Outdoor Temperature Degrees (
o
F)
% Heating Capacity
Outdoor Temperature Degrees (
o
F)
% Heating Capacity
35% 50% 65% 79% 91% 100% 100% 100% 100%
HEATING CAPACITY
-13.0 -4.0 5.0 14.0 23.0 32.0 41.0 50.0 69.8
0%
20%
40%
60%
80%
100%
120%
-15 -5 5 15 25 35 45
Outdoor Temperature Degrees (
o
F)
% Heating Capacity
36% 50% 64% 78% 88% 97% 100% 100% 100%
Outdoor Temperature Degrees (
o
F)
% Heating Capacity
MUZ-GE09NA2
MUZ-GE12NA2