M-Series MZ-GE Engineering Manual
Table Of Contents
- Contents
- 1. INDOOR UNITS
- 2. OUTDOOR UNITS
- 3. SYSTEM
- 3-1. SPECIFICATIONS
- 3-2. EXTERNAL DIMENSIONS
- 3-3. CENTER OF GRAVITY
- 3-4. ELECTRICAL WIRING DIAGRAMS
- 3-5. REFRIGERANT SYSTEM DIAGRAMS
- 3-6. CAPACITY CORRECTION CURVE BY TEMPERATURE
- 3-7. CAPACITY CORRECTION TABLE BY TEMPERATURE
- 3-8. CAPACITY CORRECTION CURVE BY REFRIGERANT PIPING LENGTH
- 3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
- 3-10. CHARGE CALCULATIONS
- 3-11. AIR FLOW DATA
- 3-12. SOUND PRESSURE LEVELS
- 3-13. STANDARD OPERATION RANGE
- 3-14. MAXIMUM HEATING CAPACITY IN LOW AMBIENT TEMPERATURE
- 3-15. ACCESSORIES
M-Series - MSZ/MUZ-GENA2 Heat Pump Systems (August 2014)
MSZ-GENA2-33
© 2014 Mitsubishi Electric US, Inc.
Due to continuing improvement, above specication may be subject to change without notice.
3-9. CAPACITY CORRECTION TABLE BY REFRIGERANT PIPING LENGTH
Refrigerant piping length (one way: ft.)
25 (std.) 40 65 100
MUZ-GE09NA2
MUZ-GE12NA2
MUZ-GE15NA2
MUZ-GE18NA-1
1.0 0.954 0.878 -
MUZ-GE24NA
1.0 0.954 0.878 0.771
Model
Refrigerant piping: ft Piping size: in.
Additional
piping
Max. length
A
Additional
piping
Max. height
B
Gas Liquid
Outside
diameter
Outside
diameter
MUZ-GE09NA2
65 40
3/8 1/4
MUZ-GE12NA2
MUZ-GE15NA2
65 40
1/2 1/4
MUZ-GE18NA-1
100 50
1/2 3/8
MUZ-GE24NA
100 50
5/8 3/8
(2) Maximum Refrigerant Piping Length & Maximum Height Difference
Max. Height
difference
B
Additional Piping
Max. length
A
Indoor
unit
Outdoor unit
(1) Cooling Capacity Correction